Setting
Example:
Required function: Protective operation with manual start, with muting, 4
muting sensors, max. 30 s muting time.
Setting:
Upper switches set to "5" for both µprocessors
Lower switches set to "2" for both µprocessors
ch1
ch2
6
9
6
9
1
3
0
3
0
6
9
6
9
10
3
0
3
0
Inside view
The function setting of BH 5902 is made by 4 rotational switches behind
the frontplate (see picture). The switches on the left make the setting for
µprocessor 1 (LED run 1) and the switches on the right for µprocessor (LED
run 2). For both processors the same functions must be set. On the upper
switches (1) the main function is adjusted. On the lower switches (10) the
setting of the muting time (Protective operation) or the number of steps
(stepping operation) is adjustable.
On muting or stepping function the light curtains LC 2 and LC 3 are always
in protective operation with manual start.
Protective operation without muting
0 LC 1
Plate
LC 2
LC 3
1 LC 1
LC 2
LC 3
Protective operation with muting
2
3
4
5
Stepping operation
6
7
8
9
33
Switch 10: Start mode and feedback input
0
1
2
3
without feedback
input
Auto
Auto
Auto
Manu
Auto
Auto
not
Manu
Manu
Auto
allowed
Manu
Manu
Manu
(fault 5)
Manu
Auto
Auto
Manu
Manu
Auto
a = maximum muting time
b = maximum synchronising time
0
1
2
LC S1 Auto,
muting 2 sensors
LC S1 Manu,
muting 2 sensors
LC S1 Auto,
muting 4 sensors
LC S1 Manu,
muting 4 sensors
Stepping operation, contact type 1,
Start-sequence: stepping and start
Stepping operation, contact type 2,
Start-sequence: stepping and start
Stepping operation, contact type 1,
Start-sequence: start and stepping
Stepping operation, contact type 2,
Start-sequence: start and stepping
4
5
6
7
8
with feedback input
Auto
Auto
Auto
Manu
Auto
Auto
not
Manu
Manu
Auto
allowed
Manu
Manu
Manu
(fault 5)
Manu
Auto
Auto
Manu
Manu
Auto
Switch 10:
3
4
5
6
7
8
9
Switch 10: Number of steps
0
1
2
3
4 - 9
BH 5902/01MF2 / 26.01.21 en / 296A