Application Examples Operation Mode 6, 7, 8: Stepping Operation
L+
start
A1+ X44
S43
BH5902
A2-
M1
L-
Picture 6: Stepping operation with 3 light curtains
L+
start
A1+ X44
S43
BH5902
A2-
M1
L-
Picture 7: Stepping operation with 3 light curtains and contact reinforcement by external contactors, 2-channel operation
(switching of feedback input can also be used at protective operation with muting)
The feed back circuit of the external relays is only tested when the module is started by pressing the push button. When using this
circuit the safe function has to be tested in regular intervalls. This can be done by interrupting a light curtain so that a reset requires
activation of the start button. activating the module is only possible when all external relays are de-energized.