Characteristic
Continuous current limit curves depend on the ambient temperature
250
200
150
100
50
0
0,1
0,3 0,5
1
switching current A
safe breaking, no continuous arcing,
max. 1 switching cycle / s
Arc limit curve
3
5
10
Application Examples
L1
On
A1(+) T11
X2
X1 T34 T12 T22
BN5930.48
A2
PE(-)
N
Two-channel emergency stop circuit
Suited up to SIL3, Performance Level e, Cat. 4
L1
On
A1(+) T11
X2
X1 T34
BN5930.48
A2
PE(-)
N
One-channel emergency-stop circuit. This circuit does not have any red-
undancy in the emergency-stop control circuit.
Suited up to SIL2, Performance Level d, Cat. 3
L1
K4
On
K5
A1 (+)
T11
X2
X1
T34
BN5930.48
A2
PE(-)
N
Contact reinforcement by external contactors, 2-channel.
The output contacts can be reinforced by external contactors with
positively driven contacts for switching currents > 10 A. Functioning of
the external contactors is monitored by looping the NC contacts into the
closing circuit (terminals X1 - X2).
Suited up to SIL3, Performance Level e, Cat. 4
15
Emergency
stop
Auxiliary
Safety contacts,
contacts,
positively drivent
positively
driven
13
23
41
42
14 24
M10653
Emergency
Auxiliary
Safety contacts,
stop
contacts,
positively drivent
positively
driven
13
23
T12 T22
41
42
14 24
M10656
Emergency
stop
13
23
T12 T22
41
42
14
24
K5
K4
M10654_a
BN 5930.48 / 22.01.19 en / 106A
33
34
33
34
33
34