Configuring the Heat Pump Heating System

6 Configuring the Heat Pump Heating System
The menus for "Outputs", "Inputs" and "Special functions" as well
as the extended setting menu can be set at the configuration
level. The extended menu level for technicians is called by

6.1 Settings

Depending on the system configuration, the full "Settings" menu
contains the following inquiries:
All manuals and user guides at all-guides.com
System-specific parameters
Menu for setting the time. An automatic
changeover from daylight saving time
(summer) to winter time can be selected.
Level for setting operating modes
Selects the operating mode
It is also possible to make changes directly
using the modus button.
Duration of party mode in hours
After the set period has elapsed, the system
returns automatically back to automatic
operation again.
Duration of vacation mode in days
After the set period has elapsed, the system
returns automatically back to automatic
operation again.
The 2nd heat generator is only necessary as of
a particular limit temperature depending on the
dimensioning of the heat pump system. The
2nd heat generator is not switched on until the
temperature sinks below the set limit
temperature.
Settings for heating circuit 1
The following heating regulation options are
available for heating circuit 1:
* Return temperature regulation based on the
external temperature and the set heating curve
* Return temperature regulation via a fixed-
setpoint (horizontal heating characteristic
curve)
* Return temperature regulation based on the
room temperature in a reference room
The heating curve end point should be set
according to the design of the heating system.
This should be done by entering the maximum
return temperature, which is the product of the
maximum calculated flow temperature minus
the temperature difference in the heating
system (spread).
Sets the desired return set temperature when
fixed-setpoint regulation is selected
simultaneously pressing the button combination (MENU) and
(ENTER
) (for approx. 5 seconds)
Select the desired menu item with the arrow buttons and confirm
with the ENTER button (
).
Setting range
International 24 h
display
Cooling
Summer
Auto
Party
Vacation
HG2
0
... 4 ...
72
0
... 15 ...
150
-20 °C
... -5 °C ...
+20 °C
External
temperature
Fixed-setpoint
Room temperature
20 °C
... 30 °C ...
70 °C
15 °C
... 40 °C ...
60 °C
6.1
Display
Always
Always
Always
Always
Always
Bivalent or mono
energy
Heating circuit 1
Heating circuit 1
Room temperature:
Not bivalent-
regenerat.
Not heating circuit 3
or
silent cooling
Heating circuit 1
Regulation according
to external
temperature
Heating circuit 1
Heating circuit 1
fixed-setpoint
E-7