1 Important Information

During commissioning, observe the respective national
safety
regulations
and
regulations, particularly VDE 0100, as well as the technical
connection requirements of the utility companies (EVU) and
network operators!
The heat pump manager should only be operated in dry
rooms with temperatures ranging between 0 °C and 35 °C.
Ensure that no condensation forms on the device.
All sensor connection leads can be extended in accordance
with the electrical documentation to up to 50 m with
0.75 mm² Cu cables with routing type B2 and an ambient
temperature of 35 °C. Sensor leads should not be installed
next to power cables.

2 Heat Pump Manager: Scope of Supply

Heat pump manager with casing
3 dowels (6 mm) with screws for wall mounting
Sensor for the outside temperature, demand sensor

3 Assembly

3.1 Attaching the wall-mounted heat pump manager (heating)

The controller is attached to the wall with the 3 screws and
dowels (6 mm) included in the scope of supply. The following
installation procedure must be followed to avoid soiling or
damaging the controller:
Mount the dowels for the upper fastening eyelet at operator
level.
Screw the screw into the dowel so that the controller can be
mounted.
Mount the controller by the upper fastening eyelet.
Mark the position of the side drill-holes.
Unhook the controller.
Mount the dowels for the side drill-holes.
Remount the controller at the top and tighten the screws.
EN-2
All manuals and user guides at all-guides.com
the
applicable
VDE
safety
452115.66.29 FD 9504
To ensure that the frost protection function of the heat pump
works properly, the heat pump controller must remain
connected to the power supply and the flow must be
maintained through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed.
Therefore,
resistance of the measuring instrument, a voltage can also
be measured when the contacts are open. However, this will
be much lower than the line voltage.
Terminals J1 to J11, J24 - J26 and the terminal strip X3 of
the heating controller N1 are connected to a low voltage
supply. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will
be destroyed.
Operator's manual and operating instructions for users
Installation and commissioning instructions for technicians
Electrical documentation