english
1. TECHNICAL DATA
As a stove of construction type 1, it is possible to connect it
to the chimney together with an exisiting other stove or
another hearth for solid fuels, as long as the chimney
dimensioning complies with DIN 4705, Part 3.
TECHNICAL DATA
Height
Width
Depth
Weight
Flue pipe outlet diameter
Nominal thermal output (EN 13240)
Maximum thermal capacity
Smallest heating capacity
Room heating capacity
(depending on building insulation)
2. IMPORTANT INFORMATION
The installation and operation information given here is of
general nature. National and European standards, local and
building regulations as well as fire prevention laws must be
observed during the operation of the stove.
General safety instructions for the
operation of your stove
Thoroughly read the entire manual before starting up
your stove and observe the caution notices.
Your heating unit may not be moved without approved
means of transport with sufficient load-bearing capacity.
Your heating unit is not suitable to be used as a stand or
as a ladder.
Please keep in mind that your
stove's surface heats up considerably
during
operation.
We
recommend wearing a safety mitten
when operating your stove.
Attention – stove varnish is no rust prevention!
Make your children aware of this particular danger and
keep them at a distance from the heating unit whenever it is
in operation.
Only burn approved fuels and materials listed in the
chapter "Clean Burning".
The burning or placing of flammable or explosive
materials, like empty spray cans and such like into the
firebox as well as the storage of such materials in the
immediate vicinity of your heating unit is strictly forbidden
due the danger of explosion.
Do not wear loose or flammable clothing when adding
fuel to the fire.
Placing non-heat-resistant objects on the heating unit or
in the vicinity of the heating unit is forbidden.
955 mm
618 mm
422 mm
165 kg
150 mm
6 kW
8 kW
3,5 kW
65-165 m³
therefore
5
Exhaust values for multiple use of the chimney in
accordance with DIN 4705, Part 3 and for the calculation
of the chimney measurements in accordance with DIN
4705, Part 2
Fluegas mass flow
Fluegas temperature
Minimum feed pressure
Nominal thermal output
Do not lay laundry onto the stove for drying. Laundry
hung up to dry must be kept at a safe distance from the
stove because of the danger of fire.
This stove is tested as a "Zeitbrand-Feuerstätte"
(intermittent burning device), which means that a continual
operation can only be achieved by a constant putting more
wood on fire.
During the operation of your heating unit it is forbidden to
use flammable or explosive materials in the same or an
adjacent room to the one in which your heating unit is
located.
The appliance must be operated with the stove door
closed.
The stove door and all fittings for adjusting the stove
must be closed, if the appliance is out of use.
Setting up your stove
Required safety distances
see name plate - in Fig. 2)
a – toward the front in the radiated area > 1100 mm
b – to the side > 600 mm
c – to the back > 150 mm
Corner installation:
a – toward the front in the radiated area >1100 mm
b – to the side > 150 mm
Make sure that the room in which the stove is set up has at
least one door or window into the outside or is directly
adjacent to such a room. Other fireplaces and extractor
hoods must not be operated in the same room as the stove.
Dexter S3
6,41
closed
closed
302 °C
closed
11 Pa
at 0.8 times n. ther.
9 Pa
outp.
(Minimum distances –
g/s