France Air COCOON Notice Technique page 50

Centrale double flux haut rendement
Table des Matières

Publicité

WORD ID
91
DP _SUPPLY
92
DP _EXHAUST
93
FLOW_SUPPLY
94
FLOW_EXHAUST
95
FAN_HOURS_H
96
FAN_HOURS_L
97
ALARMS 2
98
PRE_HEAT
99
POST_HEAT
50 ___________________________________________________________________________ NT 1603 F – 02/2019
FORMAT
B13: COMM_X570_DPE_FAIL
B14 : DPSUPPLY_FAIL
(Pa)
(m³/h)
(m³/h)
(65536 h)
(h)
B00: CONFIGURATION_FAIL
B01: ANTI ICE_FAIL
(%)
(%)
DESCRIPTION VALEURS AU DEMARRAGE OU
R/W
A LA DECONNEXION
PANNE CAPTEUR DE PRESSION
REFOULEMENT
PANNE CAPTEUR DE PRESSION REPRISE
R
POUR GROUPE COP = VALEUR DE PRESSION
COTE VENTIALTEUR REFOULEMENT
R
POUR GROUPE COP = VALEUR DE
PRESSION CÔTÉ VENTILATEUR REPRISE
POUR GROUPE CAV = VALEUR DE DÉBIT
R
CÔTÉ VENTIL. REFOULEMENT
R
POUR GROUPE CAV AVEC DOUBLE
SONDE = VALEUR DE DÉBIT CÔTÉ VENTIL.
REPRISE
R
TEMPS DE FONCTIONNEMENT
(FAN_HOURS_H * 65536+ FAN_HOURS_L )
R
R
ERREUR DE CONFIGURATION
ALARME ANTI-GLACE
R
POURCENTAGE RÉGLAGE
PRÉCHAUFFAGE MODUL.
POURCENTAGE RÉGLAGE POSTCHAUFFAGE
MODUL.