France Air COCOON Notice Technique page 48

Centrale double flux haut rendement
Table des Matières

Publicité

WORD ID
53 TIMER
54 SPEEDS REMOTE CONTROL
81 TEMP_E
82 TEMP_R
83 TEMP_X
84 TEMP_I
85 TEMP_W
86 STATUS_FLAGS
48 ___________________________________________________________________________ NT 1603 F – 02/2019
FORMAT
0- 14400 (sec.)
B00- 06: REMOTE_SUPPLY_SPEED R/W
0- 100%
B07: SUPPLY_SPEED_REMOTE_CONTROL
0: OFF
1: ON
B08- 14: REMOTE_ EXHAUST_SPEED
0- 100%
B15: EXHAUST_SPEED_REMOTE_CONTROL
0: OFF
1: ON
(0,1 °C)
(0,1 °C)
(0,1 °C)
(0,1 °C)
(0,1 °C)
B00: BYPASS
B01: SUPPLY_SPEED_REM_CONT_ACTIVE
B02: EXHAUST_SPEED_REM_CONT_ ACTIVE
B03: -
B04: NOFROST_ACTIVE
B05: -
B06: EXT_DI_PIR_MIN
B07: EXT_DI_REMOTE_OFF
B08: HEAT\COOL_1
DESCRIPTION VALEURS AU DEMARRAGE OU
R/W
A LA DECONNEXION
PRÉSENT)
R/W MINUTEUR VITESSE MAXIMALE
VENTILATEURS
PARAMÉTRE POUR LIBÉRER LA VITESSE
DES VENTILATEURS DU CONTRÔLE ET
LES PILOTER INDÉPENDAMMENT. ACTIVÉ
PAR LE BIAIS DES BIT 07 (REFOULEMENT)
ET 15 (REPRISE). PAR LE BIAIS DE 00- 06
E 08-14, LA VITESSE D'UN EST
RÉINITIALISÉE.
R
TEMP. EXTERNE
R
TEMP. REPRISE
R
TEMP. EXPULSÉE
R
TEMP. DISTRIBUTION
R
TEMP. BATTERIE À EAU
R
ÉTAT BY-PASS : 1=OUVERT ; 0=FERMÉ
VENTILATEUR INDEPENDANT DE SOUFFLAGE
ACTIF
VENTILATEUR INDÉPENDANT REPRISE ACTIF
-
SYTEME ANTI-GEL ACTIF
ÉTAT ENTRÉE NUMÉRIQUE : HUMIDITÉ
ÉTAT ENTRÉE NUMÉRIQUE : PIR
ÉTAT ENTRÉE NUMÉRIQUE : À DISTANCE
ÉTAT STADE 1 POST-CHAUFF./REFR.