WORD ID
20 PARAMETERS_FLAG
24 UNIT_1_MAX_FILT_HOURS
25 UNIT_2_MAX_FILT_HOURS
26 UNIT_3_MAX_FILT_HOURS
27 UNIT_4_MAX_FILT_HOURS
COMMAND
51 SPEED_SET_POINT
52 TEMPERATURE_SET_POINT
NT 1603 F – 02/2019 ___________________________________________________________________________ 47
FORMAT
B15: R/W WR_SP (1=WRITE PENDING)
B00- 01: R/W SEASON
0: SEASON_ND
1: SEASON_WINTER
2: SEASON_SUMMER
B02- 03: R/W BYPASS
0: BYPASS_AUTO
1: BYPASS_OFF
2: BYPASS_ON
0- 199 (500h)
0- 199 (500h)
0- 199 (500h)
0- 199 (500h)
FOR VARIABLE SPEED VERSION:
0-100 % ; 101=TIMER ; 102=AUTO
FOR THREE SPEED VERSION:
1-2-3 ; 4=TIMER ; 5=AUTO
FOR CAV\COP UNITS :
PASCAL-M3\H
TIMER(65534)
AUTO(65535)
OFF(<=48) or 50- 300 (0,1 °C)
DESCRIPTION VALEURS AU DEMARRAGE OU
R/W
A LA DECONNEXION
BIT POUR MÉMORISER EN NOVRAM LES
POINTS DE CONSIGNE (SI=1).
RÉGLAGE BY-PASS
SAISON (B00 B01)
0=NON DÉF.\AUTO
1=HIVER
2=ÉTÉ
UNIVERSAL(B02 B03)
0=NON DEF.\AUTO
1=OFF
2=ON
R/W SEUIL ALARME FILTRES HEURES GROUPE 1
R/W SEUIL ALARME FILTRES HEURES GROUPE 2
R/W SEUIL ALARME FILTRES HEURES GROUPE 3
R/W SEUIL ALARME FILTRES HEURES GROUPE 4
R/W POINT DE CONSIGNE VITESSE VENTILATEURS
PAR GROUPE VA :
0- 100 % ; 101=PROGRAMME HORAIRE
02=AUTO.
POUR GROUPE 3 VITESSE : 1-2-3
4= PROGRAMME HORAIRE
5=AUTO
POUR GROUPE CAV \ COP : PASCAL-M3
\H MINUTEUR(65534)
AUTO(65535).
R/W POINT DE CONSIGNE TEMPÉRATURE
(UNIQUEMENT SI POST-TRAITEMENT AIR