France Air COCOON Notice Technique page 49

Centrale double flux haut rendement
Table des Matières

Publicité

WORD ID
87
SPEED_C_VALUE
SPEED_D_VALUE
88
89 AUTO_INPUT_VALUE
90
NT 1603 F – 02/2019 ___________________________________________________________________________ 49
FORMAT
B09: HEAT_2
B10: TEMP_WATER_LOW
B11: EXT_DI_SUMMER
B12: EXT_DI_FIRE
B13: EXT_DI_WATER_NOFROST
B14: EXT_DO_AUTO_COMPARE
IF FANS_FAIL_TACH (REG 7 –B08) IS SET TO 1
RPM, OTHERWISE %
IF FANS_FAIL_TACH (REG 7 –B08) IS SET TO 1
RPM, OTHERWISE %
(%)
B00: COMM_X540_FAIL
B01: TE_FAIL
B02: TR_FAIL
B03: TX_FAIL
B04: FILTERS_FAIL
B05: FANS_FAIL
B06: AUTO_FAIL
B07: TI_FAIL
B08: COMM_X531_FAIL
B09: TW_FAIL
B10: TW_LOW
B11: AUTO_TO_FAIL
B12: COMM_X570_DPS_FAIL
DESCRIPTION VALEURS AU DEMARRAGE OU
R/W
A LA DECONNEXION
ÉTAT STADE 2 POST-CHAUFF.
ÉTAT ANTI-GEL BATTERIE À EAU
ÉTAT ENTRÉE NUMÉRIQUE : SAISON
ÉTAT ENTRÉE NUMÉRIQUE : FEU
ÉTAT ENTRÉE NUMÉRIQUE : ANTI-GEL
BATTERIE À EAU
ÉTAT SORTIE NUMÉRIQUE : AUTO
VITESSE VENTILATEUR REFOULEMENT
R
EN TOURS OU POURCENTAGE
(VOIR REGISTRE 7- B08)
R
VITESSE VENTILATEUR REPRISE EN
TOURS OU POURCENTAGE
(VOIR REGISTRE 7- B08)
R
POURCENTAGE VALEUR LECTURE :
SONDE QUALITÉ AIR (=%2000 PPM)
HUMIDITÉ
SIGNAL EXTERNE
R
ERREUR DE COMMUNICATION CARTE X540.
PANNE LIGNE SONDE EXTERNE.
PANNE LIGNE SONDE REPRISE.
PANNE LIGNE SONDE SOUFFLAGE.
ALARME FILTRES BOUCHÉS.
PANNE VENTILATEURS.
PANNE SONDE QUALITÉ AIR/HUMIDITÉ.
PANNE LIGNE SONDE DISTRIBUTION.
ERREUR DE COMMUNICATION CARTE X531.
ALARME GLACE BATTERIE À EAU.
ALARME TIME-OUT SONDE QUALITÉ
AIR/HUMIDITÉ.
ERREUR DE COMMUNICATION CARTE X570
REFOULEMENT.
ERREUR DE COMMUNICATION CARTE X570
REPRISE.

Publicité

Table des Matières
loading

Table des Matières