Siemens PolyCool CPS 40 Manuel D'installation Et D'utilisation page 34

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Picture Function Parameter
1)
4
REFRIG
2)
5
ENABLE
4)
6
CAP
7
SENSOR
34/124
Building Technologies
HVAC Products
Configuration mode CONF
(Continue with <OK> / picture 3)
In this mode, you enter the refrigerant used in your plant.
Additionally, it is possible to select the units of pressure,
temperature and EIV. You can also configure the types of
sensors according to your specific application.
An incorrect entry for the refrigerant can damage your
plant!
Optionally, it is possible to configure the control of the
cooling capacity (refer to chapter 6). The controller by default
comes with capacity control deactivated.
Code
Refrigerant type REFRIG R22, R23, R134a,
Enable/disable
COMP
compressor and
Fb
EIV feedback
Application
-
Sensor 1
X1
Sensor 2
X2
Sensor 3
X3
CPS40
Adjustable range/
increment
R152a, R170, R290,
R401a, R401b, R401c,
R402a, R402b, R404a,
R406a, R407a, R407b,
R407c, R408a, R409a,
R410a, R410b, R417a,
R502, R507, R600,
R600a, R717, R723,
R744, R1270
ON (for C1)
3)
ON/OFF
NO = simple superheat
(Application 1)
EXT = External
capacity control
(Application 2)
INT = Internal capacity
control (Application 3)
QBE9101-P10U with
4...20 mA output
Ni1000
0...10 V, 4...20 mA
Setting
Procedure
Default
NA
Set with +/-
Confirm
with <OK>
Exit with
<ESC>
ON
OFF
NO
-
Ni1000
0...10 V
CE1U3372XX / H 74 319 0555 0 a
22.09.2006