5.3 Mapping MODBUS

La table ci-dessous reprend les adresses permettant la consultation et/ou la modification des données du
produit, la consultation ou la modification du tariff du produit se fera depuis l'adresse @2200.
The below table gives all product data addresses allowing value reading or writing, the remote modification of
the tariff mode of the product will be possible through address @2200.
Register
Contents
Address
1018
Meter ID
1020
Baud Rate
1066
S0 output rate
107A
Combined Code
1510
LCD cycle time
2000
Voltage
2020
Grid Frequency
2060
Current
2080
Total Active Power
20A0
Total reactive power
20C0
Total Apparent Power
20E0
Power Factor
2200
Tariff
3000
Total Active Energy
3100
T1 Total Active Energy
3200
T2 Total Active Energy
3020
Forward Active Energy
3120
T1 Forward Active Energy
3220
T2 Forward Active Energy
3040
Reverse Active Energy
3140
T1 Reverse Active Energy
3240
T2 Reverse Active Energy
3060
Total Reactive Energy
3160
T1 Total Reactive Energy
3260
T2 Total Reactive Energy
3080
Forward Reactive Energy
3180
T1 Forward Reactive Energy
3280
T2 Forward Reactive Energy
30A0
Reverse Reactive Energy
31A0
T1 Reverse Reactive Energy
32A0
T2 Reverse Reactive Energy
Combined code
Le produit permet le choix du mode de calcul des index d'énergie, selon la prise en compte voulue par
l'utilisateur de la bi directionnalité de l'énergie :
The product allows the calculation choice of the total energy index, considering that the product allow
measurement of both energies flows:
Code Total (active) energy
C-01
C-04
C-05 (Default)
C-06
C-09
C-10
Datablock
Read/Write
s
Read/write
01
Read/write
01
Read/write
02
Float - Big Endian (ABCD)
Read/write
01
Read/write
01
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
01
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Read
02
Float - Big Endian (ABCD)
Forward only
Reverse only
Forward + Reverse
Reverse - Forward
Forward - Reverse
Forward - Reverse
HEX response
Value must be in range 001 - 247
Signed
9600 (default), 4800, 2400, 1200,
Signed
10000, 2000, 1000 (default), 100,
Signed
01, 04, 05 (default), 06, 09 and 10
0~30 (seconds, 30 seconds
Signed
Signed
Options for write
(default last digit SN)
600, 300
10, 1, 0.1, 0.01
default)