SOFT-STOP SETTING
Set DIP3 to ON, active procedure (DL1 flashing) - Start with the sliding gate open
VERY IMPORTANT: DIP3 must be brought from OFF to ON with the board powered.
Close the AP/CH contact or press the OP/CL pushbutton: the operator will start closing the gate until the Closing Limit Switch
(CLS) is reached.
Once the Closing Limit Switch (CLS) is reached, the operator will reverse the cycle and start opening the gate:
1_ Close the AP/CH contact or press the OP/CL pushbutton when the desired start point of the Soft-stop is reached;
2_ Once the Opening Limit Switch (OLS) is reached, the gate will stop. DL1 LED will turn ON (start point set);
3_ If the STOP contact is opened the procedure is interrupted, the gate will stop and DL1 LED will flash to advise that the
procedure is still active (Close the AP/CH contact or press the OP/CL pushbutton to restart the procedure from the be-
ginning).
4_ At the end of the operation leave DIP3 in ON !!! (If it returns to OFF and then to ON, the operations described above must
be repeated);
Note: SOFT-STOP settings apply both to opening and closing.
ATTENTION: to modify the SOFT-STOP settings it is necessary to repeat the whole procedure.
K100M FEATURES
DL1 LED
Other than indicating the programming of a transmitter is going on, DL1 LED advises error messages as follows:
Steady light:
Fast flashing:
Slow flashing:
Contact Technical Service;
6 flashes:
Make sure the gate slides smoothly and without obstacles in both directions;
7 flashes:
Perform learning procedure.
8 flashes:
Check wiring - Make sure the motor can rotate freely; Check the position of the SENS trimmer.
Multiple errors are indicated by a 2" pause between error messages. Messages will be shown until a complete opening/closing
cycle is performed.
In the event of 3 consecutive activations (during the same closing manoeuvre) of the amperometric control (obstacle detection),
the control unit opens completely on the next manoeuvre. To reset, the automation must complete a manoeuvre (opening
and then closing); otherwise the end stop search process will be repeated after each activation of the amperometric control.
In the event of activation (during the opening manoeuvre) of the amperometric control (obstacle detection), the control unit
closes approx. 20 cm. stopping the automation. On the next manoeuvre the control unit closes completely.
WARNING: the control panel logics may interpret mechanical friction as an obstacle.
ADVANCED FUNCTIONS
Clock function: a timer can be connected to the open-close pushbutton in order to keep the gate open at certain times during
the day, after which it reverts to automatic closing.
Note: The gate remains open as long as the OP/CL input continues to be activated.
433.92 MHz BUILT-IN RADIO RECEIVER
The built-in radio receiver can store up to 30 different codes from Rolling Code transmitters (S2RP, S4RP, K-SLIM-RP, T-4RP).
The radio channel directly commands the control board for opening the automatic device.
LEARNING PROCEDURE FOR TRANSMITTERS
REMOTE CONTROL LEARNING = OPENS/CLOSES
RADIO+OP/CL = PEDESTRIAN
1_ press and release the RADIO button on the control unit;
2_ DL1 LED turns OFF to indicate that the programming mode has been activated (if no code is entered within 10 seconds, the
control unit will exit the programming mode);
3_ press and release the transmitter button;
4_ DL1 LED turns ON again to indicate that the new code is stored (if this does not happen, wait 10 seconds and start again
from point 1);
5_ to store other transmitters, repeat the procedure from point 1 up to a maximum of 30 transmitters;
6_ if you wish to store the pedestrian control, repeat the procedure in point 1 pressing the RADIO+OP/CL 1 keys together
instead of the RADIO key;
7_ to exit the programming mode without storing a code, press and release RADIO button.
Note: When the maximum number of transmitter (30) is reached, the DL1 LED will start flashing fast for about 3",
without performing memorisation.
Normal operation;
Soft-Stop learning procedure activated;
Automatic 50 / 60 HZ Frequency Detection Error;
obstacle present after 1 closing attempt;
No learning procedure executed;
No motor signal;