Kübler CODIX 52P Mode D'emploi page 7

Afficheur de position électronique et fréquencemètre électronique

Publicité

Les langues disponibles
  • FR

Les langues disponibles

4. Setting of the operating parameters
a. Press both front side keys keys and switch on
the supply voltage or, if the supply voltage is
already on, press both keys simultaneously
during 5 s.
b. The display shows
c. After releasing the keys, the display shows
c1. Hold the left key pressed and press the right
key to leave the programming operation.
c2. Press the right key to switch to
d. Hold the left key pressed and press the right
key to switch to the first parameter.
e. After releasing the keys, the display alternates
between the menu title and the current menu
item. After pressing any key, only the menu
item setting is displayed.
f. Pressing the right key, the menu item setting
will be switched to the next value.
If figures are to be input (e.g. when setting the
scaling factor), select first the decade using the
left key, and then set the value using the right
key.
g. Hold the left key pressed and press the right
key to switch to the next menu item.
h. The last menu title "EndPro" allows, when
selecting "YES", to exit the programming
menu and to take over (store) the new values.
If "no" is selected, the programming routine is
repeated, the latest values set remaining
active. They can now be checked again or
modified.
5. Programming routine
The programmable parameters of the device are
described below, in the order in which they can
be set. The device is fully programmed after one
pass of the routine.
The first values stated correspond to the factory
settings
5.1 Polarity of the inputs
npn: switching for 0 V
pnp: switching for +U
5.2 Switching on the 30 Hz filter (INP A, INP B)
The filter provides input damp-
ing*
30 Hz filter off (f
30 Hz filter on
5.3 Input mode
Count input and count direction
input
INP A: Count input
INP B: Count direction input
Differential input
IINP A: count input adding
INP B: count input subtracting
Totalising
INP A: count input adding
INP B: count input adding
Quadrature input
INP A: count input 0°
INP B: count input 90°
Quadrature input with pulse
doubling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A will
be counted
Quadrature input with pulse
quadrupling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A and
INP B will be counted.
For the frequency
measurement, INP C may be
operated independently of the
counter input modes.
* where bounce occurs, e.g. with contacts
B
)
max
2