20
UK
10 - DIP SWITCH DIP2
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
DIP
Function
FUNCTIONING
changing this setting will
2_4
reset the control board and a
new learning cycle will be
required.
2_5
UNUSED
WARNING LIGHT
2_6
/
FLASHING LIGHT
PAUSE TIME
2_7
LEARNING
FINAL STROKE
2_8
IN CLOSING
DECELERATION
DISTANCE
changing this setting will
2_9
reset the control board and a
new learning cycle will be
required.
2_10
SOFT STOP
11 - JUMPER SW4
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
JUMPER
Function
FUNCTIONING
SW4
TERMINAL 21
Status
ON
ENCODER
OFF
TIME
ON
OFF
Terminal M2_7 and M2_8 work as WARNING LIGHT
ON
Terminal M2_7 and M2_8 work as FLASHING LIGHT
OFF
ON
PAUSE TIME LEARNING ENABLED
OFF
STANDARD OPERATION
Enables the final stroke in closing function.
Operation:
After slowing down, the movement continues in slow down mode for 1s to facilitate
ON
the locking of the electric lock.
During the final stroke in closing the safety devices and the commands are not
active (PHOTO, EDGE, START, etc.)
Disables the final stroke in closing function
OFF
Long deceleration (~33% of the total stroke).
ON
Irrelevant if DIP2_4=OFF
Short deceleration (~25% of the total stroke)
OFF
Enabling of an additional deceleration ramp at the end of the motion next to the
ON
mechanical limit switch in opening or closing.
Not enabled if it is time operation (DIP2_4=OFF)
Disables the Soft Stop function
OFF
Status
Description
N.C. devices are connected to STOP/EDGE (21) input
8,2KOhm (8K2) resistive devices are connected to STOP/EDGE (21) input.
Description