Annexe B
•
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the Manufacturer Ins-
tructions, National Electrical Code and any additional local codes, or the equivalent.
Table for input fusing of inverters F5 – A – housing, stand-alone drive units:
Variateur
05F5
05F5
05F5
07F5
07F5
07F5
09F5
*) The voltage rating of the Class rated fuses shall be at least equal to the voltage rating
of the Drives.
Branch Circuit Protection: Type E Self Protected Manual Motor Controllers for
inverters F5–A housing, stand-alone drive units::
Cat. No.
05F5
05F5
07F5
07F5
Cat. No.
05F5
07F5
09F5
# all Drives series which use a Self Protected Motor Controller rated 480Y/277V are suitable
for 480Y/277V sources only.
Use of Modular Drive System 07F5A1A-3E2F:
Tension d'entrée
240 1ph
240 3ph
400/480 3ph
240 1ph
240 3ph
400/480 3ph
400/480 3ph
Drive input rating
240V 1ph
240V 3ph
240V 1ph
240V 3ph
Drive Input
rating #
400/480V 3ph
400/480V 3ph
400/480V 3ph
UL248 Fuse
Class J or RK5 *
[V]
Self Protected Manual Motor
Controller Type and manufac-
turer
PKZMO-10E, Eaton Industries
PKZMO-6.3E, Eaton Industries
PKZMO-16E, Eaton Industries
PKZMO-10E, Eaton Industries
Self Protected Manual Motor
Controller Type and manufac-
turer
PKZMO-10E, Eaton Industries
PKZMO-10E, Eaton Industries
PKZMO-10E, Eaton Industries
UL248 Fuse
Class CC *
)
[A]
10
6
5
15
10
6
10
Self Protected Ma-
nual Motor Controller
rating
230V/1ph, 1.5 hp
230V/3ph, 1.5 hp
230V/1ph, 2 hp
240V/3ph, 3 hp
Self Protected Ma-
nual Motor Controller
rating
480Y / 277V, 3 hp
480Y/277V, 7.5 hp
480Y/277V, 7.5 hp
)
[A]
10
5
5
20
10
6
10
F - 29