3. Recommendations on the boiler
a. Installation and maintenance of the U-bend
Fill the U-bend with water before commissioning and before
measuring combustion
Allow for a slope after the U-bend to encourage the run-off of
condensates by gravity
Clean the U-bend (at least once a year)
If a condensates neutralisation station is installed:
Keep the neutralisation station flat beneath the level of the
U-bend outlet
Condensates must be able to run off naturally from the
boiler outlet to the neutralisation station
b. Maintenance of the condenser
Check the condition of the condenser and clean it with water
(at least once a year)
Check that there are no leaks on the condenser, particularly
on the hatch. When refitting the hatch:
Check the hatch gasket
(replace if necessary, ref SPC 300007086)
Check for leaks (gasket + hatch) using graphite silicon
available as a spare part (ref PR 300012077)
4. Recommendations on the stove fitting
Do not exceed the maximum authorised stove fitting length
The installation of 45° elbows is preferable to 90° elbows
Do not fit 90° elbows in series
Construct the horizontal sections on the flue gas side with a 3%
slope towards the boiler
Do not brick in the flue gas conduit (damps noise transmission
phenomena in the building caused by vibration)
Fix the concentric conduits to the wall using clamps and
bracket(s) (limits stress on the conduits during start-up)
Fix the conduit coming
into the sleeve with
the 3 self cutting
screws (delivered
with the sleeve).
6