ELECTRIC CONNECTIONS

The unit must be connected directly
to an electrical outlet or to an
independent circuit.
The FCL cassette fan coils must be
powered with 230V ~ 50Hz current
and have an earth connection. The
line voltage must remain within the
tolerance of ±10% with respect to the
nominal value.
In order to protect the unit against short
circuits, mount a max. 2A 250V (IG)
magnet circuit breaker omnipolar
B
22
AGLLRIJ 0907 - 4528560_03
switch on the power supply line with
a minimum contact opening distance
of 3 mm.
The electrical power supply cable must
be of the H07 V-K or N07 V-K type
with 450/750V insulation if inside
a tube or raceway. Use cables with
double H5VV-F type insulation for
visible cable installation.
For the connections, refer to the fan coil
wiring diagrams.
A
C
230VAC