Télécharger Imprimer la page

Jenn-Air CCGP2420P Mise En Service page 6

Publicité

Les langues disponibles

Les langues disponibles

Pressure Testing
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5 kPa).
This appliance, as well as its individual shut-off valve,
must be disconnected from the gas supply piping system
during any pressure testing of the system at test
pressures in excess of 1/2 PSIG (3.5 kPa).
When checking appliance regulator function, make certain
pressure of natural gas supply is between 6 and 14
inches of water column or, if converted for LP gas,
between 11 and 14 inches.
Electrical Wiring Information
This appliance is equipped with a grounded type power
cord. A grounded outlet must be provided.
The power cord extends 45² outside the unit housing. The
outlet should be located inside the cutout width and below
the lowest most projection of the unit housing.
User may experience occasional circuit tripping if Ground
Fault Circuit Interrupter (GFCI) outlet or breaker is in use.
Electrical Grounding Instructions
This appliance is equipped with a three prong grounding
plug for your protection against shock hazard and should
be plugged directly into a properly grounded receptacle.
Do not cut or remove the grounding prong from this plug.
This appliance must be disconnected from its electrical
supply at the wall receptacle before servicing the
appliance.
Converting Appliance For Use
With LP Gas
Propane conversion is to be performed by a JENN-AIR
AUTHORIZED SERVICER (or other qualified agency) in
accordance with the manufacturer's instructions and all
codes and requirements of the authority having
jurisdiction. Failure to follow instructions could result in
serious injury or property damage. The qualified agency
performing this work assumes responsibility for this
conversion.
Electrical power and gas must be turned off prior to
conversion.
This appliance was adjusted at the factory for use with
natural gas. To convert it for use with LP gas (propane or
butane), each of the following modifications must be
performed:
A. Replace all orifice spuds
Step 1: Remove the grates and burner heads.
Step 2: Remove aluminum venturi tube.
Step 3: Trim a small piece of masking tape to the
size of a dime and affix it over the end of a
5/16² nut driver.
Step 4: Firmly press the nut driver over the orifice
spud (figure 10) and loosen spud by turning
counterclockwise. Carefully lift nut driver out
of burner throat. Orifice spud should be
captured in the recess. Repeat this step for
each burner.
REMOVAL OF ORIFICE SPUD
ALUMINUM VENTURI
BURNER BASE
6
5/16² NUT DRIVER
PIECE OF MASKING
TAPE STUCK TO END
OF DRIVER
IGNITER
ORIFICE SPUD
FIGURE 10

Publicité

loading

Ce manuel est également adapté pour:

Ccgp2720pCcgp2820p