Carrier 80HMA Mode D'emploi page 32

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 75
Variable table
Nr.
Name
Par.
Define how often (days) the
Anti-
disinfection cycle starts. If 0
82
legionella
is selected Disinfection is not
Period
performed
Anti-
The day time when the Anti-
83
legionella
legionella can start
Start time
Anti-
Setpoint for Anti-legionalla
84
legionella
Temperature (°C)
Temperature
Anti-legionella cycle is consider
Anti-
completed if the Sanitary
85
legionella
temperature is reached the
Wait Time
Anti-legionella setpoint for this
time (min)
Anti-
If Anti-legionella cycle is not
86
legionella
completed within this time (hr),
time over
it is considered failed
Defines how many heaters,
could be ON at the same time.
0. All (BackUp and Sanitary
Heaters)
1. Max 3 Heaters. Priority on
BackUp Heaters
2. Max 3 Heaters. Priority on
Electrical
Sanitary Heaters
91
Heater Priority
3. Max 2 Heaters. Priority on
BackUp Heaters
4. Max 2 Heaters. Priority on
Sanitary Heaters
5. Max 1 Heaters. Priority on
BackUp Heaters
6. Max 1 Heaters. Priority on
Sanitary Heaters
Outdoor Air
Outdoor air temperature
Temperature
threshold to allow backup
92
Threshold
heaters ON. Below heaters are
for BackUp
allowed (°C)
Heaters
Temperature hysteresis on
Water
the water in tank to turn on
Temperature
the backup heaters (°C). If the
93
Hysteresis
Water temperature is below the
for BackUp
requested setpoint minus this
Heaters
value, the Heaters are allowed
to be turned on
Delay for
Delay to start backup heaters
94
BackUp
when the other conditions
Heaters
request them (min)
Outdoor Air
Outdoor air temperature
Temperature
threshold to turn on the boiler
101
Threshold for
and turn off the heat pump. Below
Boiler
only boiler can operate (°C)
Water temperature to active
Antifrost
the Antifrost routine to avoid to
102
SetPoint
freeze the water in the tank and
pipes (°C)
% of the maximum frequency
Frequency
103
for the Frequency Reduction
Reduction
mode (only 30AWH)
20 80HMA
Description
Master
x
x
x
x
x
Aux heaters
x
x
x
x
System control
x
x
x
Available on
User
Heat
Slave Pool
Interface
Pump
x
x
RANGE
MIN
MAX DEFAULT
0
7
0
0
24
3
60
90
75
5
30
30
2
12
4
1
7
0
-30
25
4
0
10
3
0
60
10
-30
10
-5
-10
10
4
50
100
100

Publicité

Table des Matières
loading

Table des Matières