4.
Mark the screw centres through the holes in the fan back plate. Drill, plug and
screw into position.
5.
Wire the fan as described in Section B-Wiring. Adjust any settings as
required (see Section C-Setup).
6.
After installation, ensure impeller rotates freely.
7.
Replace the grille and tighten the retaining screw.
WINDOW MOUNTING
For window mounting refer to the instructions provided with the kit.
B. WIRING.
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT
MUST BE ISOLATED FROM THE POWER SUPPLY DURING
INSTALLATION OR MAINTENANCE.
IMPORTANT
• The cross - sectional area of supply cord used should be ranged from 1 -1.5mm 2 .
• The extraction fan or transformer (SELV models) is suitable for connection to 220-
240V 50Hz supply.
• The Transformer (SELV models only) MUST be surface mounted to allow air
to freely circulate around the unit. When installed in a loft void it MUST NOT be
enclosed or covered with insulation.
• The fan is a class ll double insulated product and MUST NOT be earthed.
1.
Select and follow the appropriate wiring diagram. (Fig. 1, 2, 3, OR 4, 5, 6)
2.
Check all connections have been made correctly and ensure all terminal
connections and supply wires are securely fastened.
3.
Ensure the impeller rotates and is free from obstructions.
C. SETUP
Accessing the commissioning menu
To configure the fan first remove the grille. With the grille removed the control board is
visible (Fig.7). Do NOT isolate the fan from the power supply as
configuration requires power to the fan; removing the grille will
automatically stop the impeller from spinning.
Once the fan has been commissioned please write
the installation date in the box on the label provided.
IMPORTANT
Do NOT attempt to remove the circuit board cover (Fig.7). This covers
the high voltage power supply, preventing the risk of an electric shock.