14.5
Simulation
The simulation mode enables LUC-T functions
to be simulated and checked.
Errors and warnings in V9H0
• E613: Display during simulation. Returns to
normal operation after simulation.
Simulation off: V9H6: 0
• On power failure the instrument
automatically returns to normal operation!
Simulation of height
#
VH
Entry
1
V9H6
1
H
Simulation height
2
V9H7
e. g. 2.000
H
Simulated height
(6.600 ft)
(e. g. 2 m/6.6 ft)
3
V9H8
Display of current (also shown on
bargraph)
V0H0
Display of height, level or volume
4
V9H6
0
H
Simulation off
Simulation of current
#
VH
Entry
1
V9H6
3
H
Simulation current
2
V9H7
e. g. 14
H
Simulated current
(e. g. 14 mA)
3
V9H8
Display of current (also shown on
bargraph)
4
V9H6
0
H
Simulation off
Simulation of volume
#
VH
1
V9H6
2
2
V9H7
e. g.
100.0
(26.40
USgal)
3
V9H8
Display of current (also shown on
bargraph)
V0H0
Display of volume (If no linearization
curve has been entered then volume
corresponds to level.)
Text
4
V9H6
0
14.6
Locking
Locking via the keyboard
When the instrument is locked via the
keyboard, both keyboard and display
parametration as well as all parametrations via
the handheld terminal etc. are blocked.
It can only be unlocked using the keyboard.
Text
The matrix can be again locked once all
parameters have been entered.
• Locking by entering a three-figure code
number not equal 333.
#
VH
1
V9H9
e. g. 332
2
The number 332 is shown in V9H9.
All matrix fields are blocked except V9H9.
#
VH
1
V9H9
333
2
The number 333 is shown in V9H9.
Matrix fields are no longer blocked.
• Locking by using the keyboard(see note on
Entry
Text
H
Simulation volume
H
Simulated volume
(e. g. 100 l /
26.4 USgal)
H
Simulation off
Entry
Text
H
Locking
Entry
Text
H
Unlocking
locking via the keyboard).
P = Protect
Locking
display approx.
P---
V
H
0 2
2 s
9999 displayed
in V9H9.
+
V
H
F = Free
Unlocking
display approx.
F---
V
H
0 2
2 s
333 displayed in
V9H9
+
H
V
e
27