RedLINK™ Installation Guide (TrueZONE™)
System test
Follow the procedure below to test for proper operation.
To begin, press and hold the s and t buttons
until the display changes (about 3 seconds)
System Test
02
Wireless test
10
Heating system
20
Emergency
heating system
30
Cooling system
40
Fan system
70
Thermostat
information
(for reference only)
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection (minimum off time)
is bypassed during testing. To prevent equipment damage, avoid cycling the compressor
quickly.
69-2090EFS—09
M28488
System Status
0 Off
1 Test radio signal (after a brief pause, screen displays 1-10
to show signal strength; 5 or higher recommended)
0 Heat and fan turn off
1 Heat turns on
2 Stage 2 heat turns on
3 Stage 3 heat turns on
0 Heat and fan turn off
1 Heat and fan turn on
0 Compressor and fan turn off
1 Compressor and fan turn on
2 Stage 2 compressor turns on
0 Fan turns off
1 Fan turns on
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System test
number
02
Done
Press s or t to check system status
Press
next
Press
done
10
System
status
Back
to advance to next test
to terminate system test
0
Next
M28489