Overview
7. Air duct connection
When the volume of the room where your thermodynamic water heater is installed is less than 20m
be connected to air ducts with a diameter of 160mm. If the air ducts are not insulated, condensation may
appear on them during operation. It is therefore imperative to opt for insulated air ducts.
OUTLET
Ducting must be directly
connected
to
the
directional air inlets and
outlets.
When connected to ducts, it is necessary to set the regulator accordingly.
The total pressure drop of the ducts and accessories for release and suction of the air must not
exceed 130 Pa. The maximum duct lengths must be respected.
Poor ducting (crushed ducts, excessive length or number of elbows ...) can result in reduced performance and
malfunctions. As a result, we do not recommend using flexible ducts.
Installation
Crushed ducts:
Use
Maintenance
Non-insulated ducts:
Warranty
EN
3
, it can
59