Commissioning and operation
34
5.4.3
Procedure for setup via interface and PC software supplied:
NOTICE
In order to be able to use this function, the unit must already be created in the PC database
or has to be created beforehand.
1.
Connect the unit interface (RS232 / RS485, USB or Ethernet) to the PC.
2.
Start the PC software and create a new unit in the PC database:
- Select "Unit -> Display/change unit setup/Add new unit"
- Select "Unit -> Add new unit"
- Enter unit identifier. To transmit the unit setup select the corresponding unit
interface. Confirm with "Next". Select the corresponding interface parameters (must
match the settings for communicating at the device). Confirm with "Next". A summary
of the information on the new unit is displayed. When you click "OK", a connection is
established to the unit and the new unit is created in the PC database.
3.
Adjust the unit settings and select "Finished -> Send setup to unit". The new setup
parameters are automatically transferred to the unit.
4.
Finally, the unit settings should be saved in the unit database. Select "Finished -> Save
setup in unit database".
5.4.4
Setup via SD card
Save the unit settings on the PC onto the SD card using the PC software supplied. This setup
file can then be imported into the unit.
NOTICE
In order to be able to use this function, the unit must already be created in the PC database
or has to be created beforehand. In addition, there has to be an SD card slot on the PC.
CAUTION
!
Never remove the SD card from the unit without previously launching the function "Extras –
> SD card –> Remove safely" as data could be lost otherwise.
Procedure for setup using an SD card:
1.
Copy setup to SD card:
- Insert a formatted SD card into the unit.
- In the Extras menu, select "SD card -> Save setup".
– In the Extras menu, select "SD card –> Remove safely".
– Remove the SD card from the unit and insert it into the SD card slot at the PC.
2.
Start the PC software and create a new unit in the PC database:
– Select "Unit –> Display/change unit setup/Add new unit"
– Select "Unit –> Add new unit"
– Enter unit identifier. Select "Parameter file from a data source (e.g. diskette, ATA
Flash, CF, SD)" to transmit the unit setup. Confirm with "Next". Select the corresponding
unit parameter file (*.rpd) from the SD card. Confirm with "Next". A summary of the
information on the new unit is displayed. When you click "OK", the new unit is created
in the PC database.
3.
Adjust setup in the PC program and save in the associated database:
- Adjust the unit settings.
– Select "Finished –> Save setup in unit database". The new setup parameters are saved
in the PC database. Transfer the new SETUP file to the SD card in your PC: select
"Finished –> Create setup data carrier (diskette/ATA flash/CF/SD)" and select the
suitable drive.
– Remove the SD card from the slot in the PC and insert it into the unit.
4.
Read in new setup directly at the unit:
– In the Extras menu, select "SD card –> Load setup". To remove the SD card, select "SD
card –> Safe removal" in the Extras menu. Repeat these steps to configure additional
units with this setup.