3.2
Installation instructions
3.2.1
Mounting tool
To install in the control panel, all you need is a screwdriver.
3.2.2
Panel mounting, Installation dimensions
195.2
(7.69)
Fig. 2:
Panel mounting and installation dimensions. All dimensions in mm or (inch)
• Installation depth without terminal cover: approx. 158 mm (6.22") (incl. terminals and
fastening clips)
• Installation depth with terminal cover: approx. 197 mm (7,76")
+1
• Panel cutout: 138
x 138
• Panel thickness: 2 to 40 mm (0.08 to 1.58")
• Max. viewing angle range: from the display central axis 50° in all directions
• Securing to DIN 43 834
1.
Push the unit through the panel cutout from the front. To avoid heat accumulation, we
recommend keeping a distance of > 15 mm (>0.59 inch) from the walls and other units.
2.
Hold the unit horizontally and then hang the two jack screws into the openings (either
as shown in figure 3 the upper opening on the left and the lower opening on the right
side of the housing, or use the openings on top and bottom of the housing).
+1
+0.04
+0.04
mm (5.43
x 5.43
5
141 (5.55)
27
(0.2)
(1.06)
37.07
157.4 (6.20)
(1.46)
192.3 (7.57)
196 (7.72)
58
138 (5.43)
(0.28)
")
Installation
25