Mechanical Mounting - VALPES VRX Serie Documentation Technique Mise En Service

Actionneur electrique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Mechanical mounting (VRX models)
DIMENSIONS OF THE ACTUATOR
The actuator is set to its closed position in our factory.
Possible fixations : F05 (4xM6 with Ø50) and F07 (4xM8 with Ø70), star 17, depth 19mm.
Do not mount the actuator « upside down ».
Necessary height above the valve for the mounting of the actuator : H=300mm.
EMERGENCY MANUAL OVERRIDE
In case of an electric supply failure, it is possible to operate the actuator manually :
Turn the knob (appendix p.31 mark 9) to position MAN and hold it in position.
Turn the outgoing drive shaft of the actuator with the help of an adjusting spanner.
In order to re-engage the reduction, release the knob.
MOUNTING / DISASSEMBLY OF THE COVER AND POSITION INDICATOR
For the wiring and setting of the actuator, it is necessary to remove the cover.
Mounting of the cover (appendix p.31 mark 2) : make sure that the seal ring (appendix p.31 mark 7) is correctly placed in its
position, mount the cover and tighten the 4 screws M6 (appendix p.31 mark 3, torque : max. 6Nm).
Mounting of the position indicator (appendix p.31 mark 1) : fit the indicator onto the outgoing axle.
DSBA3401 - Révision : 09/02/2011
VALPES
VALPES
VALVE CONTROL SYSTEM
VALVE CONTROL SYSTEM