POSI models - Electric connection

RESPECT SAFETY INSTRUCTIONS
Our cable glands (appendix p.31/32 mark 15) are designed for cables with a diameter between 7mm and 12mm. The used
cables must be able to withstand the ambient conditions (maximum temperature 70°C).
Remove the position indicator, unscrew the four screws and take off the cover.
POWER SUPPLY WIRING
Ensure that the voltage indicated on the actuator ID label (appendix p.31/32 mark 11) corresponds to the voltage supply.
Connect to earth through the exterior bolt M5 located under the cable gland (appendix p.31/32 mark 16). For multivolt ver-
sion, it is also possible to connect the actuator to earth inside the actuator through the bolt M3 next to the terminal strip.
Unscrew the left cable gland and insert the cable.
Connect the wires to the power supply card's terminal strip (appendix p.31/32 mark 14).
N
-
1
15V-30V 50/60Hz (12V-48V DC)
100V-240V 50/60Hz (100V-350V DC)
Put a lacing cord around the wires (see the picture beside) and re-tighten the cable
gland.
POSITIONING CARD WIRING (OUTPUT AND INPUT SIGNAL)
In order to avoid electromagnetic perturbations, it is compulsory to use shielded cables (cables longer than 3m).
Unscrew the right gland and pass the cable.
Connect the input signal between terminals 15 and 16 (appendix p.27 mark B).
Terminal 15 is the negative polarity (-) and terminal 16 is the positive polarity (+).
Connect the output signal between terminals 13 and 14 (appendix p.27 mark B).
Terminal 13 is the positive polarity (+) and terminal 14 is the negative polarity (-).
Tighten the cable gland.
Factory setting : by default, 4-20mA input and output signals with normal rotation sense.
To proceed to a new setting of the card : please see next page, "Parameter selection sequence".
To check the proper operation of the card : please see next page, "Normal operating mode".
Type 0-20 or 4-20mA : 5V DC max.
The terminal temperature can reach 90°C
N.B.: The actuator is always powered, so it must be connected to a disconnection system (switch, circuit
breaker) to ensure the actuator power cut.
N.B.: The used wires must be rigid (feedback voltages : 4 to 250V AC/DC)
DSBA3401 - Révision : 09/02/2011
Ph
+
TP/PE
2
3
VALPES
VALPES
VALVE CONTROL SYSTEM
VALVE CONTROL SYSTEM
ACTUATOR PRE-SET IN FACTORY
Earth round
terminal
Clamping
ring
P. 22/35