IN2 : Input of the external set value control in « Constant pressure » and « P.I.D. control » mode
Set value 4-20mA
100%
Set value
in % of the range
of measurement of
the sensor
0
2
4
IN2 : Input of external frequency control in « Speed control » mode
External Signal 0-20mA
100%
Frequency
of the converter
~30%
0
2
4
External Signal 4-20mA
100%
Frequency
of the converter
~30%
0
6
POMPES SALMSON SAS 04/2013
Area where converter stops
Safety
area
20
Input current (mA)
Area where converter stops
Safety
area
20
Input current (mA)
Area where converter stops
Safety
area
20
10
Input current (mA)
Set value 0-10V
100%
Set value
in % of the range
of measurement of
the sensor
0
1
2
External Signal 0-10V
100%
Frequency
of the converter
~30%
0
1
2
External Signal 2-10V
100%
Frequency
of the converter
~30%
0
3
Area where converter stops
Safety
area
10
Input voltage (V)
Area where converter stops
Safety
area
10
Input voltage (V)
Area where converter stops
Safety
area
10
5
Input voltage (V)