Installation and Operating Instructions
EN
Central ventilation units KWL EC.. D Pro/WW
1.12 Technical data
KWL EC 700 D Pro
Voltage/Frequency
Rated current – ventilation
Rated current – pre-heater
Max. total rated current
Pre-heater (outlet)
Aux. heater (outlet) kW
Electrical supply line to UV
Air flow rates Vm
3
/h
KWL EC 700 D Pro WW
Voltage/Frequency
Rated current – ventilation
Rated current – pre-heater
Max. total rated current
Pre-heater (outlet)
Aux. heater (outlet) kW
Electrical supply line to UV
Air flow rates Vm
3
/h
KWL EC 1400 D Pro
Voltage/Frequency
Rated current – ventilation
Rated current – pre-heater
Max. total rated current
Pre-heater (outlet)
Aux. heater (outlet) kW
Electrical supply line to UV
Air flow rates Vm
3
/h
KWL EC 1400 D Pro WW
Voltage/Frequency
Rated current – ventilation
Rated current – pre-heater
Max. total rated current
Pre-heater (outlet)
Aux. heater (outlet) kW
Electrical supply line to UV
Air flow rates Vm
3
/h
KWL EC 2000 D Pro
Voltage/Frequency
Rated current – ventilation
Rated current – pre-heater
Max. total rated current
Pre-heater (outlet)
Aux. heater (outlet) kW
Electrical supply line to UV
Air flow rates Vm
3
/h
KWL EC 2000 D Pro WW
Voltage/Frequency
Rated current – ventilation
Rated current – pre-heater
Max. total rated current
Pre-heater (outlet)
Aux. heater (outlet) kW
Electrical supply line to UV
Air flow rates Vm
3
/h
230 V~/50 Hz
Wiring diagram
Permissible air temperatures
2.6 A
Weight
12.2 A
Standby losses
14.8 A
Design
2.2 kW
--
NYM-J
510 - 330 - 210
230 V~/50 Hz
Wiring diagram
2.6 A
Permissible air temperatures
12.2 A
Weight
14.8 A
Standby losses
2.2 kW
Design
2.3 (at 60/40 °C)
2.1 (at 50/40 °C)
1.3 (at 40/30 °C)
NYM-J
510 - 330 - 210
3N~ 400 V/50 Hz
Wiring diagram
6.2/--/-- A
Permissible air temperatures
--/11.3/11.3 A
Weight
Standby losses
6.2/11.3/11.3 A
Design
4.5 kW
--
NYM-J
1000 - 650 - 400
3N~ 400 V/50 Hz
Wiring diagram
6.2/--/-- A
Permissible air temperatures
--/11.3/11.3 A
Weight
6.2/11.3/11.3 A
Standby losses
4.5 kW
Design
4.7 (at 60/40 °C)
4.2 (at 50/40 °C)
2.7 (at 40/30 °C)
NYM-J
1000 - 650 - 400
3N~ 400 V/50 Hz
Wiring diagram
6.2/--/-- A
Permissible air temperatures
10.1/10.1/10.1 A
Weight
16.3/10.1/10.1 A
Standby losses
Design
7.0 kW
--
NYM-J
1800 - 1150 - 720
3N~ 400 V/50 Hz
Wiring diagram
6.2/--/-- A
Permissible air temperatures
10.1/10.1/10.1 A
Weight
16.3/10.1/10.1 A
Standby losses
7.0 kW
Design
8.1 (at 60/40 °C)
7.3 (at 50/40 °C)
4.6 (at 40/30 °C)
NYM-J
1800 - 1150 - 720
4
SS-1006
-20 °C to 40 °C
110 kg
< 1 W
IP20
SS-1006
-20 °C to 40 °C
115 kg
< 1 W
IP20
SS-1007
-20 °C to 40 °C
185 kg
< 1 W
IP20
SS-1007
-20 °C to 40 °C
190 kg
< 1 W
IP20
SS-1008
-20 °C to 40 °C
265 kg
< 1 W
IP20
SS-1008
-20 °C to 40 °C
270 kg
< 1 W
IP20