ZERO CLEARANCE FIREPLACE MODELS NZ-26, NZ-26WI, NZ3000, & NZ3000H-1
This kit includes:
PART #
DESCRIPTION
W010-0363
Damper plate assembly
W570-0010
#8 x ½ Hex head screws
W500-0087
Damper body
W410-0014
5ft - 8" Diameter fl ex liner
W361-0022
Insulation 8" X5' Sleeve Mylar
W615-0015
Firestop spacer
NZM218-W
White grille c/w screws
The hot air gravity vent system may be used to distribute heat
to adjoining rooms located either above or beside the room
containing the fi replace.
Vent pipe must be insulated using insulation sleeve supplied
by manufacturer. All hot air gravity vents must be insulated.
The hot air gravity vent system is not to be connected to a
central heating system.
1. Remove the upper louvres and the appropriate cover plate.
Cut a hole into the
insulation and remove
10" MINIMUM TO
COMBUSTIBLES
(Fig. 1).
(CEILING)
2. NZ-26 ONLY: To
allow the damper to
open fully, the heat
shield cover plate
must be removed (by
breaking the tabs)
before installing the
NZ220 (Fig. 2).
3. Insert the damper
body through the opening, with the
slot and 2 holes facing forward (Fig.
3). Bend out the 4 tabs. MASONRY
ENCLOSURE INSTALLATION: After
bending the damper body tabs out,
secure to the side using the cover
plate screws.
INSULATION
Fig. 3
SLEEVE
FLEXIBLE
VENTPIPE
NZ-26 ILLUSTRATED
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 0G8 Canada •
NZ220 HOT AIR GRAVITY VENT KIT
INSTALLATION INSTRUCTIONS FOR NAPOLEON
QTY
NZ-26 / NZ-26WI
DRYWALL/WALL FACING
FIRESTOP
WHITE
GRILLE
12"
Fig. 1
Fig. 2
NZ-26 STOVE TOP
HEAT SHIELD COVER PLATE
DAMPER PLATE
DAMPER
BODY
(When installed with a
masonry chimney, the hot
air gravity can only be
installed off the side.)
Install the hot air vent in an upward direction only. NEVER
INSTALL IN A DOWNWARD DIRECTION by connecting to the
opening in the bottom of the unit. For this application use the
1
NZ62CH central heating kit.
8
1
1
No more than two hot air gravity vents can be installed to
1
the fi replace. Individual vent runs must not exceed 10 feet.
1
1
If the fi replace enclosure is to be masonry instead of framed
with combustible materials, the vent(s) must be side-installed.
A 1" clearance from the insulation sleeve to combustibles
is required.
Grille to be installed on wall a minimum of 5 feet above the
fl oor.
4. Taking the damper plate assembly, rod side up: insert the rod
end through the hole at the rear of the damper body and the handle
end through the slot. Keep the bracket to the outside of the damper
body. Align the holes in the bracket with the 2 holes in the body and
tighten with 2 of the screws supplied.
5. Slide the insulation sleeve over the fl ex liner. Expose one end of
the liner, place over the damper body and secure using 3 screws.
Push the sleeve down over the liner.
6. Being careful not to compress or damage it, extend the liner to the
required length (Fig. 4). If the fi nal grille location requires more than
5 feet of liner, use extension kit NZ220-2, pipe coupler W175-0002,
and vent support assembly W010-0067 (not supplied). Expose the
liner, place through the framing, over the fi restop spacer assembly
and secure using 3 screws. Pull the sleeve up over the liner.
7. Attach the fi restop spacer assembly to the framing front.
8. Once desired wall facing is
completed, attach grille. Do
not block or restrict grille
opening.
9. Manually balance the
damper setting to suit your
requirements. This may take
a few attempts; thereafter
adjustments should no
longer be required as is
normally experienced with
your central heating system
registers.
1(866)820-8686
5 FT MINIMUM
FROM FLOOR
Fig. 4
SECOND
STOREY
GROUND
12" MINIMUM
FLOOR
PIPE TO CEILING
5 FT MINIMUM
FROM FLOOR
NZ-26 ILLUSTRATED
W415-0073 / F / 02.14.20
•