6.4-Earth Resistance Display/Switch and Terminal Settings
The earth resistance test is a 3-wire test consisting of two test stakes and the earth electrode under test.
This test requires an accessory stake kit. Connect as shown in right figure.
Best accuracy is achieved with the middle stake at 62 % of the distance to the far stake. The stakes should
be in a straight line and wires separated to avoid mutual coupling.
The earth electrode under test should be disconnected from the electrical system when conducting the
test. Earth resistance testing should not be performed on a live system.
6.5-To Measure Earth Resistance
1-Turn the rotary switch to the RE position.
2-Press and release TEST button. Wait for the test to complete.
The primary (upper) display shows the eart resistance reading.
The Test Current will be displayed in the secondary display.
If Voltage detected between the test rods greater than 10V, the test is inhibited.
6.6-RE Function Menu Operation
Main Display
F1 Button: None
F2 Button: None
F3 Button: None
F4 Button: Short the F4 button 3S, triggering zero function.
Up Button: None
Down Button: None
Enter Button: None
6.7-Using the LOW OHM Function
26
A continuity test is used to verify the integrity of connections by making a high resolution resistance
measurement. This is especially important for checking Protective Earth connections.
6.8-LOW OHM Function Menu Operation
Main Display
Menu Display
F1 Button: Pop-up and shutdown LOW OHM menu, Shutdown mode is activated when the user selects.
F2 Button: Pop-up and shutdown LOW OHM menu, Shutdown mode is activated when the user selects.
F3 Button: None
F4 Button: Short the F4 button 3S, triggering zero function.
Up Button: Up menu to select the current active sub-options.
Down Button: Down menu to select the current active sub-options.
Enter Button: Confirm the user select mode.
13/08/2017 Version No. 001
13/08/2017 Version No. 001
Multifunction Installation Tester/English
27