Multifunction Installation Tester/English
Accuracy of the Current of the RCD: ± (5% of reading + 1digits)
Resolution of the RCD Timing: 0.1ms
Voltage and Frequency
Measurement Range
Resolution(V)
Accuracy
(V)/AC-DC
80~500
1
±(2% of reading +2digits)
Measurement Range
Resolution(Hz)
Accuracy
(Hz)
45~65
1
±2Hz
Insulation
Range
Terminal Voltage
Resolution
125V(0%~+10%)
0.125~4.000 M
0.001M
4.001~40.00 M
0.01M
40.01~400.0 M
0.1M
400.1~1000 M
1M
0.250~4.000 M
0.001M
250V(0%~+10%)
4.001~40.00 M
0.01M
40.01~400.0 M
0.1M
400.1~1000 M
1M
0.500~4.000 M
0.001M
500V(0%~+10%)
4.001~40.00 M
0.01M
40.01~400.0 M
0.1M
400.1~1000 M
1M
1.000~4.000 M
0.001M
1000V(0%~+10%)
4.001~40.00 M
0.01M
40.01~400.0 M
0.1M
400.1~1000 M
1M
Low Ohm
Range
Resolution
Accuracy
0.000~2.000
0.001
±(1.5%+30)
2.00~20.00
0.01
±(1.5%+3)
20.0~200.0
0.1
200~2000
1
±(1.5%+5)
Earth Resistance
R ange
R esolution
Accuracy
0.00~99.99
0.01
±(2%+30d)
100.0~999.9
0.1
±(2%+6d)
1000~2000
1
4
Accuracy
Test Current
Short circuit
current
± 3%+10)
1mA @load125k
≤1mA
±(2%+10)
±(4%+5)
±(5%+5)
±(3%+10)
1mA @load250k
≤1mA
±(2%+10)
±(3%+2)
±(3%+2)
±(3%+10)
1mA @load500k
≤1mA
±(2%+10)
±(3%+2)
±(4%+5)
±(3%+10)
1mA @load1M
≤1mA
±(2%+10)
±(3%+2)
±(4%+5)
Max. Open Circuit Voltage
Overload Protection
5.0V±1VDC
250Vrms
13/08/2017 Version No. 001
3-General Specification
Power Source
8 x 1.5V AA Size Alkaline batteries
or 8 x 1.2V AA Size rechargeable Ni-MH batteries
Battery Life
Average of 15hours
CAT Rating
CAT III 600V
Protection Classification
Double Insulation
Protection Rating
IP65
LCD Screen Type
3.5"TFT
Pixels
320x240
Operating Temp
0°C~ 45°C
95% 10°C~ 30°C: Non-condensing
Relative Humidity
75% 30°C~ 40°C
Storing Temp
-10°C~ 60°C
Operating Altitude
2000m
Protective device
500mA Fast response BS 88 Fuse
Dimensions
24.2cm(L) x 10.5cm(W) x 14.5cm(H)
Weight
1.56kg
4-Instrument Overview
4.1-Front View
1-Starts the selected test. The T key is surrounded by a "touch pad". The touch pad measures the potential
between the operator and the tester's PE terminal. If you exceed a 100 V threshold, the D symbol above
the touch pad is illuminated.
2-Warning lamp
3-320X(RGB)X240 color active matrix
4-Press and hold Turns the tester on and off. Short Press return the latest status.
5-Function selector switch.
6-Navigation keys:
Enter, Up, Down, Left/Save, Right
7-Selects the sub-menus from the Test Mode selected by the rotary switch:
F1, F2, F3, F4
8-Accesses help menus and delete files.
1
6
2
7
13/08/2017 Version No. 001
Multifunction Installation Tester/English
5
3
8
5