EN
A
PICTURES
[1] KNX RS485 Motor Controller WM,
wall mounted version (ref. 1860236)
[2] KNX RS485 Motor Controller PCB,
PCB version (ref. 1860238)
B
MOUNTING
Choose the optimal location: flat and large sur-
face, open the housing.
[1] Mount the KNX RS485 Motor Controller
[2] Mount the DIN rail version
1.
Vertical (wall mounted or PCB version)
2.
Horizontal (wall mounted version)
C
WIRING
[1] Finish wiring and connect KNX bus
[2] Insulated screwdriver
[3] Wiring diagram
[4] Check the correct running directions of the end
product
UP: the end product goes up ( C + )
STOP: the end product stops ( C + + )
DOWN: the end product goes down ( C + )
[5] Possible switches
1.
Inteo Centralis IB, Ref. 1810138
2.
Double push button
VERDRAHTUNG KABELING CABLE
Anschluss an ...
Forbindelse til ...
Connection to ...
RS485 bus
Modular Jack 8P4C (RJ45)
spring clamp terminal
Switches
spring clamp terminal
KNX bus
D
CONFIGURATION
[1] KNX Prog button
[2]
Leitung
Kabel
Cable
Min.: 4 x 2 x 0.5 mm/24 AWG
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 0.8 mm/20 AWG
2 x 0.8 mm/20 AWG
1.
Wall mounted version
2.
PCB version
1.
The stub must not exceed 10 m.
2.
The length of the RS485 bus must not
exceed 1000 m.
3.
Not more than 6 RS485 motors may be
connected together and only motors of
the same type!
Type and length of the used end product
must be the same.
Verdrilltes Adernpaar
Parsnoet
Twisted pair
Required twisted pair shielded,
impedance 100 Ω (-10 Ω/+30 Ω),
recommended CAT5-FTP,
following Somfy RS485 guidelines
Recommended
Required, following
KNX topology guidelines
animeo KNX RS485 MOTOR CONTROLLER. REF. 5113740 C -
Max. Länge
Maks. længde
Max. length
1000 m
100 m
-
6/12