AME 25, AME 35
ENGLISH
Safety Note
To avoid injury of persons and
damages to the device, it is absolutely
necessary to read and observe these
instructions carefully.
Necessary assembly, start-up, and maintenance
work must be performed by qualified and
authorized personnel only.
Please comply with the instructions of the
system manufacturer or system operator.
Do not remove the cover before the
power supply is fully switched off.
Disposal instruction
This product should be dismantled
and its components sorted, if possible,
in various groups before recycling or
disposal.
Always follow the local disposal regulations.
Mounting
Fix the actuator on the valve ❶
Admissible Installation Positions ❷
Wiring
Do not touch anything on the PCB!
Switch off the power line before wire
the actuator! Lethal voltage!
Wire the actuator according to the wiring
diagram.
Control signal
Control signal from the controller must be
connected to terminals Y (input signal) and SN
(common) on the AME printed board.
Output signal
Output signal from the terminal X can be used
for indication of the current position. Range
depends on the DIP switch settings.
Supply voltage
Supply voltage (24 V~ –15 to +10 %, 50 Hz) must
be connected to the terminals SN and SP.
DIP switch settings
U
I
2 V_---V
0 V_---V
Direct
Inverse
---
Sequential
0(2) V_5(6) V
5(6) V_10 V
Proportional
3 point/RL
LOG. flow
LIN. flow
100 % k
RED. k
VS
Reset
Reset
Part Name
Lead (Pb)
Mercury (Hg)
Housing
X
Bushings
X
Clamp
X
Yoke
X
O: Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X: Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirement in GB/T 26572;
EI.LF.M1.2V
Factory settings:
ALL switches are on OFF position! ❹①
Note: All combinations of DIP switches are
allowed. All functions that are selected are added
consecutively. There is only one logic override of
functionalities i.e. the switch No.6 Proportional/3
point, which sets actuator to ignore control signal
and works as a "simple" 3-point actuator.
SW1: U/I ❹②
Factory settings:
Voltage control signal (0-10 V).
SW2: 2-10 V/0-10 V ❹③
Factory settings:
2-10 V.
SW3: Direct/Inverse ❹④
Factory settings:
DIRECT
SW4:---/Sequential ❹⑤
Two actuators can be set to work parallel with
one control signal. If the SEQUENTIAL is set than
an actuator respowwnds to split control signal
(see 0(2)-5(6) V/5(6)-10 V).
Note: This combination works in combination
with switch No.5: 0(2)-5(6) V/5(6)-10 V
SW5: 0(2)-5(6) V/5(6)-10 V ❹⑥
Note: This function is available if switch No.4:
---/Sequential is set.
SW6: Proportional/3 point ❹⑦
Actuator needs to perform Self
stroking prior changing DIP 6 to ON.
Output signal depends on DIP 2, 3&5
setting.
Actuator can operate in modulating (DIP 6 to
OFF) or in "simple" 3-point mode, if the 3-point
function is selected (DIP 6 to ON).
Connect power supply on terminals SN and SP
terminals.
Factory set DIP 6 to OFF for operating actuator
in Modulating mode.
Actuator's stem will run to its totally extended
or retracted position by bridging SN signal to
terminals 1 or 3 and will remain in this positron
as long as potential is present.
Set DIP 6 to ON for operating actuator in 3 point
mode.
VS
Look carefully wiring diagram as wiring is
different for controllers with triac output (ECL)
in comparison to controllers with relay output.
Return signal X indicates the correct position.
Cadmium (Cd)
Hexavalent Chromium (Cr(VI))
O
O
O
O
O
O
O
O
Hazardous Substances Table
Polybrominated biphenyls (PBB)
O
O
O
O
Note: If 3 point function is selected actuator
does not respond to any control signal on port Y.
It only rises and lowers spindle if power is supplied
on port 1 or 3.
SW 7: LOG. flow/LIN. flow ❹⑧
Factory setting is:
LOG. Flow (characteristic of valve is unchanged)
Note: If this function is used in combination
with non-logarithmic valves the characteristic
of motorised valve will be anti-logarithm of
valve's characteristic (e.g. valve with linear
characteristic will be transformed to quick open
characteristic).
SW 8: 100% K
/RED. K
❹⑨
VS
VS
Note: This function works proper only with
logarithmic (equal percentage) valves.
SW9: Reset ❹⑧
After the actuator has been connected to
power supply, the actuator will start the
self-adjustment procedure. The indicator LED
flashes until self adjustment is finished. The
duration depends on the spindle travel and will
normally last a few minutes. The stroke length
of the valve is stored in the memory after self
adjustment has been completed. To restart
self adjustment, change the position of RESET
switch (switch No.9). If the supply voltage is
switched off or falls below 80 % in more than
0.1 s, the current valve position will be stored
in the memory and all data remain saved in the
memory also after a power supply cut-out.
Function test
The indicator light shows whether the
positioner is in operation or not. Moreover, the
indicator shows the control status and faults.
Constant light
- normal operation
No light
- no operation or no power supply
Intermittent light (1 Hz)
- self adjusting-mode
Intermittent light (3 Hz):
- power supply too low
- insufficient valve stroke (<20 s)
- end-position cannot be reached.
Dimensions
Polybrominated diphenyl ethers (PBDE)
O
O
O
O
© Danfoss | 2016.11 | 5
O
O
O
O