3. Briefly press the operating button to select the correct function:
■ Controller function: The CO
turn red.
■ Sensor function: The CO
4. Press the operator button for 5 seconds to confirm the selection:
■ All LEDs on the right blink green 3 times.
7.3 Control setting of the CO
Ventilation unit
Ventilation with heat recovery in combination with
ComfoZone Box
Ventilation with heat recovery
Mechanical ventilation
* The CO
Sensor uses a fixed target value of 1050ppm (parts per million: number of units
2
of CO
per million units in the measured air).
2
Function
Operation of the
setting
CO
2
Sensor
The signal from
the device is the
measured value.
(In this case, 2V
corresponds to
400ppm and 10V to
2000ppm)
The controller that
ensures that the
level of CO
not become too high
is located in the
ventilation unit.
Controller
A signal from the
device provides the
ventilation needed to
reach 1050ppm.
The ventilation unit
can be controlled via
the 0­10V input.
LED turns green, the bottom two LEDs on the right
2
LED turns red, the bottom two LEDs on the right turn red.
2
0-10V Sensor
2
ComfoAir Q settings
Sensor
■ Signal at 0%: 10V
■ Signal at 100%: 2V
■ 0­10V input function:
■ Setpoint: depending on the
■ Proportional ratio: 50%
does
2
■ Integration time: 300
■ Signal at 0%: 0V
■ Signal at 100%: 10V
■ 0­10V input function: send
Advisory setting of the CO
Sensor
■ Sensor, depending on regulations
■ Controller, unless a value other than
1050ppm* is desired
Controller
(2000ppm)
(400ppm)
control
desired CO
level, e.g. 4V
2
(800ppm)
(800ppm)
seconds
(minimum ventilation)
(maximum ventilation)
Sensor
2
ComfoAir E settings
■ Activation: On
■ Method: Setpoint control
■ Setpoint: depending on the
desired CO
level, e.g. 4V
2
(800ppm)
■ Min. setting: 2.0V
■ Max. setting: 10.0V
■ P value: 50%
■ I value: 300 seconds
■ Invert signal: Yes
■ Activation: On
■ Method: Proportional
flow rate
■ Min. Setting: 0.0V
■ Max. Setting: 10.0V
■ Invert signal: No
EN - 45