4.1.2 ADDiNg SECTiONS
Add chimney sections, according to the manufacturers installation instructions. The chimney must extend at
least, 3 feet (0.9m) above its point of contact with the roof and at least 2 feet (0.6m) higher than any wall, roof,
EN
building or obstacle within 10 feet (3.1m) horizontally.
3 FT
(0.9m)
MIN
An insulated stainless steel chimney must be supported at the ceiling or roof and its installation must comply
with its manufacturer's instructions.
W415-1133 / A / 06.12.13
2 FT (0.6m) MIN
10 FT (3.1m)
TO NEAREST
ROOFLINE
10 FT
(3.1m) OR
MORE
FLAT ROOF
REV B : Added metric dimensions
LESS THAN
10 FEET
(3.1m)
2 FT (0.6m)
RIDGE
MIN
3 FT
3 FT
(0.9m)
(0.9m)
MIN
MIN
3 FT
(0.9m)
MIN
LESS THAN
10 FEET
(3.1m)
2 FT (0.6m)
MIN
WALL
59.1b