Télécharger Imprimer la page

Siemens SITRANS DS III/P410 Notice De Service page 54

Masquer les pouces Voir aussi pour SITRANS DS III/P410:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 57
7.8
Certificates and approvals
Certificates and approvals
Classification according to Pressure
Equipment Directive (PED 97/23/EC)
Drinking water
Explosion protection
Intrinsic safety "i"
Designation
Permissible ambient temperature
Connection
Effective inner capacitance
Effective inner inductance
Flameproof enclosure
encapsulation "d"
Designation
Permissible ambient temperature
Connection
Dust explosion protection for Zone
20 and 20/21
Designation
Permissible ambient temperature
max. surface temperature
Connection
Effective inner capacitance
Effective inner inductance
Dust explosion protection for Zone
22
Designation
Connection
Type of protection "n" (Zone 2)
52
HART
for gases of Fluid Group 1 and liquids of Fluid Group 1; meets requirements of
Article 3 Para. 3 (good engineering practice)
only for flow rate:
for gases of Fluid Group 1 and liquids of Fluid Group 1; fulfills the basic safety
requirements as per article 3, Para 1 (appendix 1); classified as category III,
module H conformity evaluation by TÜV Nord
Available soon (for SITRANS P DSIII)
II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb
-40 ... +85 °C (-40 ... +185 °F) temperature class T4
-40 ... +70 °C (-40 ... +158 °F) temperature class T5
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
To a certified intrinsically safe circuit
with the max. values:
U
= 30 V, I
= 100 mA,
i
i
P
= 750 mW, R
= 300 Ω
i
i
C
= 6 nF
i
L
= 0.4 mH
i
II 1/2 G Ex d IIC T4, T6 Ga/Gb
-40 ... +85 °C (-40 ... +185 °F) temperature class T4
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
To a circuit with the operating values:
U
= 10.5 ... 45 V DC
H
II 1 D Ex ta IIIC T120°C Da
II 1/2 D Ex ta/tb IIIC T120°C Da/Db
-40 ... +85 °C (-40 ... +185 °F)
120°C (248°F)
To a certified intrinsically safe circuit
with the max. values:
U
= 30 V, I
= 100 mA,
i
i
P
= 750 mW, R
= 300 Ω
i
i
C
= 6 nF
i
L
= 0.4 mH
i
II 2 D Ex tb IIIC T120°C Db
To a circuit with the operating values:
U
= 10.5 ... 45 V DC; P
H
PROFIBUS PA and FOUNDATION
Fieldbus
FISCO supply unit
U
= 17.5 V, I
0
Linear barrier
U
= 24 V, I
0
C
= 1.1 nF
i
L
= 7 µH
i
To a circuit with the operating values:
U
= 9 ... 32 V DC
H
FISCO supply unit
U
= 17.5 V, I
0
Linear barrier
U
= 24 V, I
0
C
= 1.1 nF
i
L
= 7 µH
i
To a circuit with the operating values:
= 1.2 W
U
= DC 9 ... 32 V; P
max
H
SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
= 380 mA, P
= 5.32 W
0
0
= 174 mA, P
= 1 W
0
0
= 380 mA, P
= 5.32 W
0
0
= 250 mA, P
= 1.2 W
0
0
= 1.2 W
max
A5E03434626-04, 05/2015