Occurs if the fume
probe detects a fume
AL 3
temperature above 280°C.
HOT FUMES
The shutdown procedure
is activated.
Occurs when the fume
AL 4
extraction fan is faulty.
FAN FAIL
The shutdown procedure
is activated.
No flame in ignition stage.
AL 5
The shutdown procedure
NO IGNITION
is activated.
AL 6
Brazier not fed with pellets.
NO PELLETS
Occurs in case of
AL 7
cutting in of the auger
THERMAL
duct temperature safety
SAF
thermostat.
The system is stopped.
In the work stage the
AL 8
stove detects a pressure
NO NEG
below the vacuum switch
setting threshold.
PRESS
The system is stopped.
AL 9
Appears when the
INSUFF
combustion air flow is below a
certain threshold.
DRAUGHT
Occurs when the water
AL E
pressure does not come
WATER
within the values for
PRESSURE
correct operation.
The system is stopped.
Occurs in case of cutting
in heating chamber
AL A
water temperature safety
SAFETY H
O
thermostat with T>95°C.
2
The system is stopped.
EN
Too many pellets.
Reduced heat exchange
in the system.
The fume fan is blocked.
Faulty speed control
sensor.
No power to fume fan.
The pellet hopper is
empty.
The heater is faulty,
dirty or not correctly
positioned.
Pellet load setting
incorrect.
The pellet hopper is
empty.
The pellet loading
gearmotor has to adjust.
The gearmotor does not
load pellets.
The safety thermostat has
detected a temperature
above the setting threshold
due to overheating of
the bottom part of the
hopper blocking gearmotor
operation.
The combustion chamber
is dirty.
The fume duct is
obstructed.
The fire door is not closed.
The overpressure valves
are open-stuck.
Faulty vacuum switch.
The combustion chamber
is dirty.
The fume duct is
obstructed.
The fire door is not
closed.
The overpressure valves
are open-stuck.
Faulty air flow meter.
Occurs when the pressure
transducer on the water
circuit detects a pressure
below or above the fixed
limits.
The safety thermostat has
detected a temperature above
the setting threshold due to
overheating of the heating
chamber water blocking
gearmotor operation.
cod.48427M013_11/19
Adjust the pellet flow.
Other reinstatement operations
must be carried out by a
Service Centre.
Reinstatement operations must be
carried out by a Service Centre.
Check pellets in hopper.
Check the lighting procedures.
Other reinstatement operations
must be carried out by a
Service Centre.
Check pellets in hopper.
Adjust the pellet flow.
Other reinstatement operations
must be carried out by a
Service Centre.
Check the cause of excessive
overheating.
Reset the safety thermostat by
pressing the reset button.
Check cleanness of the fume
duct and combustion chamber.
Check hermetic closing of
the door.
Check closing of the
overpressure valves.
Other reinstatement operations
must be carried out by a
Service Centre.
Check cleanness of the fume
duct and combustion chamber.
Check hermetic closing of
the door.
Check closing of the
overpressure valves.
Other reinstatement operations
must be carried out by a
Service Centre.
Check the cause of the problem,
restoring the circuit pressure by
bringing it to the normal operating
value.
Check the cause of excessive
overheating.
Reset the relevant safety
thermostat by pressing the
reset button.
87