WARNING!
Do not cover the sauna heater. This creates a fire hazard.
Do not use your sauna heater without stones. This creates a fire hazard.
Do not touch the top of the heater. This will cause severe burns.
Incorrect ventilation or an incorrectly located sauna heater can, under
certain circumstances, cause excessive drying of the wood in the sauna
and create a fire hazard.
Cover sauna floors with a non-slip material.
Never hose down the sauna.
There must always be at least 50 mm insulation directly behind the wood
panelling in the sauna (no other material may be used, such as particle
board, plaster, etc).
Sauna doors must always open outwards. All that should be needed to
open the sauna door is just a little light pressure.
Do not use the sauna for any purpose other than sauna bathing.
Do not install more than one sauna heater in a sauna room, unless you
follow exactly the special instructions for twin-heater installations.
Sauna fragrances, etc. may ignite if poured undiluted into the stone
compartment.
Never leave young children unattended in the sauna.
Do not lift the heater in the heating elements.
Sauna bathing is not always suitable for persons in poor health. Consult
your doctor for advice.
Store this information in a safe place.
INSTALLATION
Fig. 1a.
Tylö SO sauna heater with integral control panel.
Fig. 1b.
Tylö WM sauna heater with integral control panel.
Fig. 1c.
Tylö EP 100 and EH 150 sauna heater with separate control panel.
Fig. 1d.
Tylö EZ 225 sauna heater with separate control panel.
Installing the sauna heater.
The sauna heater should be placed on the same wall as the door, see
figure 12. In an exceptional circumstance, the heater may be placed on a
side wall, but as close as possible to the wall with the door. Fit the heater
200 mm above the floor, observing the regulations for the minimum
distance to the side wall.
The heater is semi-installed to the connection box on the sauna wall. The
type of the connection cable should be H07RN-F (VSN, VSB) with rubber
insulation, or similar. Do not use a cable with PVC- insulation!
The cable or conduit is laid on the outside of any heating insulation; see
figs. 9 and 10. A single-core cable should be protected by a plastic conduit
up to the heater, or in flexible metal conduit with internal insulation.
2.INSTALLATION
2.1. Placing of the heater
The minimum safety distances given (tabel 3, fig.3-7) should be carried
out. The safety distances are also shown on the heater's nameplate. The
fastening measures for the wall bracket are shown in fig.2 (SO) and
fig 3. (WM). Do not cover the walls or the ceiling nearby the heater with
additional plates – the temperature in the wall materials can rise to a
dangerous level. When installing the heater in a niche, the niche's
minimum height should be 1900 mm and the maximum depth 500 mm.
2.2. Mounting
On the wall (SO, WM)
The heater is equipped with a removable wall bracket for easy installation
(fig. 2a), which makes it possible to fasten the screws and the wall
mounting to the wall prior to installing the heater (fig. 2b). Fastening
screws for mounting on a wooden wall are included in the delivery. Thin
wooden panels are not strong enough for a safe fastening. Use a board or
a plywood plate behind the heater to strengthen the mounting points. For
stone and brick walls, use only heat-resisting special anchor fastenings
(no fastenings with plastic plugs). The heater is lifted to its place as
shown in fig. 2c, 2d, 2e. Do not lift the heater on the heating elements or
on the upper steel panel in the back housing, but only with a good hold on
the lower and upper edge of the inner jacket. Free space for service
should be left on one side of the heater.
At the floor (EP, EH, EZ)
The heater is placed on the floor and fastened with the fastening plate of
the back foot with two screws to a wooden floor or with wedge anchors to
a stone floor.
3. Connecting to the electric power network
Before connecting the heater, check the technical specifications on the
chart. An authorised skilled electrician in accordance with the regulations
in force can only do connecting work. The heater is semi-installed to the
connection box on the sauna wall. The type of the connection cable
should be H07RN-F (VSN, VSB) with rubber insulation, or similar. Do not
use a cable with PVC- insulation! Connect the heater before installing it
on its place. Do not mount the splash-proof connecting box higher than 50
cm from the floor on the wall.
Fig. 4 – Minimum safety distances.
A = standard installation. B = recess installation. Please refer to the table
for minimum distances to side wall (X,Y). When installing sauna heaters
in a recess, the sensor (C) should be placed 250 mm from the rear wall of
the recess and 1500 mm above floor level.
Fig. 5, 6 – Minimum safety distances
Minimum distance to sauna fittings in front of a sauna heater.
Fig. 7 – Minimum safety distances
Minimum distance to sauna fittings in front of a sauna heater.
Fig. 8 – Sauna
(Sauna heater types EP, EH, EZ and control panel type CC).
1 = sauna heater. 2 = thermistor (sensor). 3 = control panel CC 10/
CC 50/ CC 100. 4 = external power switch (if any). 5 = distribution box.
6 = relay box RB30/60.
Fig. 9 – SO, WM.
A = electric conduit. B = wooden panel. C = insulation. D = built-in
sensor. F = built-in control panel. G = vent. H = wooden batten.
I = connecting box
Wiring diagram, fig. 16, 24, 28.
Fig. 10 – EP, EH and EZ.
A = electric conduit. B = wooden panel. C = insulation behind control
panel. D = sensor. E = capillary tube/thermistor wire. F = TS separate
control panel (CC panel in folded figure). G = vent. H = wooden batten.
I = connecting box
Wiring diagram, fig. 16, 24, 28.
Tabel 1, Technical data.
Weight
Heater model Output Sauna volume
without
kW
min/max m³
stones (kg)
SO 6
6,0
5-8
10,8
SO 8
8,0
7-12
11,2
WM 10
10,0
8-15
16,0
EP-100
10,0
8-15
EH-15
15,0
14-24
EZ-22,5
22,5
25-36
Amperage and conductor area:
230-
230-
kW
240V 3~
240V~
415V 3~
amp
mm²
amp
mm²
amp
6
15
2,5
26
10
10
8
20
4
35
10
12
10
25
6
44*
16*
16
15
38
16
-
-
22
22,5
56
16
-
-
32
*) 10 kW not approwed for single-phase in Europe.
Volume and minimum installation distances:
Heater
Minimum
Ceiling height
Model
A
in sauna mm
SO 6
1900
50
SO 8
1900
80
WM 10
2100
100
EP-100
1900
80
EH-15
2100
80
EZ-22,5
2300
100
(SO, WM).
(EP, EH, EZ).
Stone weight
Measurements (mm)
(max, kg)
Widht
Depth
25-30
425
390
25-30
425
390
22
370
450
11
25
360
420
19
45
480
540
27
55
560
550
400-
400-
200-
415V 2N~
208V~
mm²
amp
mm²
amp
mm²
1,5
-
-
30
10
2,5
-
-
40
16
2,5
-
-
-
-
6
-
-
-
-
10
-
-
-
-
Min. distance to the heater. mm
B
C
D
E
F
70
30
1100
150
500
80
30
1100
150
500
70
30
1350
110
80
1250
80
1320
150
1400
Height
480
480
590
650
780
900
200-
208V 3~
amp
mm²
18
4
23
6
29
10
44
16
65
25
Wall behind
the heater
20
40
40
5