Ris 700 Pe R 4.5 Eko - Salda RIS 400 PE 0,9 EKO 3.0 Manuel De Montage Et D'installation

Origine: salda.lt/en
Masquer les pouces Voir aussi pour RIS 400 PE 0,9 EKO 3.0:
Table des Matières

Publicité

21.7. RIS 700 PE R 4.5 EKO 3.0

1.737.0008A-0.1.1-L-2k
Q1
PE N
L1
X23
1
Q2
B6
2
1
2
3
4
X22.1
1
3
5
K1
2
4
6
X01
1
2
EK
RG2
X02
KE1
Color markings:
WH(BK) - White(Black)
RD - Red
GN(BU) - Green (Blue)
YE - Yellow
PV - supply air fan EC.
IV - extract air fan EC.
KE1 - supply air heater.
AT1 - automatic reset thermostat supply air heater.
RT1 - manual reset thermostat supply air heater.
TL - outside air temperature sensor.
TJ - supply air temperature sensor.
TE - exhaust air temperature sensor.
DTJ100 - extract air humidity + temperature sensor.
M1 - BYPASS damper actuator.
M2 - outside air damper actuator.
M3 - extract air damper actuator.
M5 - water cooler valve actuator.
FA - fire alarm input.
P/U - "Transsmiter 1" supply air fan pressure transmitter
(0-10 VDC).
P/U - "Transsmiter 2" extract air fan pressure, CO2
transmitters (0-10 VDC).
1 2 3 4 5 6 7 8 9 10
X16
1
2
3
4
5
X16.1
2
3
X16.2
4
5
1
Y1
Y2
G
M5
24VAC, 3-position
Y1 - OPEN (24VAC)
Y2 - CLOSE (24VAC)
Jumper
G - System potential 24VAC
Water cooler
Boost
Start/Stop
valve actuator
RIS 400-700 P EKO 3.0 v2019.06
PE
N
L
IV
GND
+
0-10V
in
2
1
F1 5 A
PE
N
L
PV
GND
+
0-10V
in
5
6
X22.2
1
AT1
C
2
K1
A1
A2
A1
1x1200W/230V
A2
1
RT1
C
2
13
K1
14
R1
A1
24VDC
A2
X16.3
7
DX Cooling
11
12
13
14
6
7
8
9
10
11 12 13 14 15 16 17
6
7
8
X16.4 9 10
11
12
13
14
X16.3
X16.4
1
P
FA
3
Jumper
AHU status
Fire alarm
DX Cooling
AHU stop
AHU work
input
24VAC, 3-position
Y1 - Control OPEN (AC 24 V)
M5
Y2 - Control CLOSE (AC 24 V)
G - System potential AC 24 V
Y1 Y2
G
X33
X16.1
1
2
3
1
2
3
4
1 - GND
5
6
2 - 24V open
7
3 - 24V close
8
24VDC
3-position
M1
X32
1
2
3
1
3
2
4
5
6
7
8
BK
RD
WH
1
2 3
4
5
6 7
...9
X3
1
2
3
RG1
11
14
X16.2
8
4
5
6
X16.4
9
10
11
12
23
1
P
3
Jumper
Transmitter 1 (24 VDC)
23 - 24V DC,
24 - intput, 0-10V DC,
25 - GND,
P - DX cooler protection, differential pressure switch.
KE1 - electrical heater 1,2kW/230V, 1f.
RG1 - PRV-V2.5.
RG2, RG3 - controllers ESKM1-26/176-30.
Q1 - disconnector.
Q2 - circuit breakers.
F1 - fuse (size 5x20).
15
16
17
18
19
20
21
22
18 19 20 21 22
X16.5
15
16
17
18
19
20
21
22
X16.6
N
L
N
L
TJ
N
L
N
L
L
M2
M3
230V AC
230V AC
ON/OFF
ON/OFF
NTC
Supply air
Extract air
Supply air
damper actuator
damper actuator
temp.sensor
230V AC
230V AC
M2
M3
ON/OFF
ON/OFF
N
L
L
N
L
L
X16.5
15 16
17
18
19
20
X37
TL
TE
X52
X21
RS485_2
RS485_1
U
TA
RH
24 25
13
14
X16.10
26
FA
P
P
Jumper
Transmitter 2 (24 VDC)
26 - 24V DC,
27 - intput, 0-10V DC ,
28 - GND,
23
24
25
26
27
28
23
24
25
26
27
28
26
27 28
X16.10
X16.4
23
24 25
P
P
Transmitter 1
Transmitter 2
26 - 24V DC,
23 - 24V DC,
27 - intput, 0-10V DC,
24 - intput, 0-10V DC,
28 - GND,
25 - GND,
Air quality transmitter
Air quality transmitter
Supply air pressure
CO2; Extract air pressure
TJ
X16.6
ModBus RTU
Remote control
27
28
FR |