Reverse Power Flow CT Connection Check Table
Reverse Power
Flow CT (L1)
No
Position
1
L1 (red)
2
L1 (red)
5
L1 (red)
6
L1 (red)
7
L1 (red)
10
L1 (red)
11
L1 (black)
12
L2 (black)
15
L2 (black)
16
L2 (black)
17
L2 (black)
20
L2 (black)
31
Poor connection
32
Poor connection
33
Poor connection
34
Poor connection
37
Poor connection
34
Reverse Power
Flow CT (L2)
Polarity
Position
Polarity
Correct
L2 (black)
Correct
Correct
L2 (black)
Reverse
Correct
Poor connection
Reversed
L2 (black)
Correct
Reversed
L2 (black)
Reversed
Reversed
L1 (red)
Correct
L1 (red)
Correct
Correct
Poor connection
Reversed
Correct
L1 (red)
Reversed
L1 (red)
Correct
Reversed
Poor connection
Reverse
Reversed
L1 (red)
-
L1 (red)
Correct
-
L2 (black)
Reversed
-
L2 (black)
Correct
-
Poor connection
Reversed
-
Correct /
Incorrect
Reverse power flow CT is installed correctly.
Correct
Check if the reverse power flow CT polarity
Incorrect (B)
(L side, K side) is correct.
Confirm the reverse power flow CT is properly
-
Incorrect (A)
connected to the cable.
Check if the reverse power flow CT polarity
Incorrect (B)
(L side, K side) is correct.
Check if the reverse power flow CT polarity
Incorrect (C)
(L side, K side) is correct.
Confirm the reverse power flow CT is properly
-
Incorrect (D)
connected to the cable.
Confirm the reverse power flow CT is
Incorrect (C)
connected to the correct cable.
Confirm the reverse power flow CT is
Incorrect (B)
connected to the correct cable.
Confirm the reverse power flow CT is properly
-
Incorrect (D)
connected to the cable.
Confirm the reverse power flow CT is connected
Incorrect (B)
to the correct cable.
Reverse power flow CT location and polarity are
Incorrect *
both reversed, however it still works.
Confirm the reverse power flow CT is connected to
the correct cable.
-
Incorrect (A)
Confirm the reverse power flow CT is properly
connected to the cable.
Confirm the reverse power flow CT is connected to
the correct cable.
Incorrect (D)
Confirm the reverse power flow CT is properly
connected to the cable.
Confirm the reverse power flow CT is connected to
the correct cable.
Incorrect (A)
Confirm the reverse power flow CT is properly
connected to the cable.
Confirm the reverse power flow CT is properly
Incorrect (A)
connected to the cable.
Confirm the reverse power flow CT polarity
(L side, K side) is properly connected.
Incorrect (D)
Confirm the reverse power flow CT is properly
connected to the cable.
Confirm the reverse power flow CT is properly
-
Incorrect (B)
connected to the cable.
Solution