Tabuchi Electric EneTelus EHW-S55P3B-PNUS Manuel D'installation page 18

Masquer les pouces Voir aussi pour EneTelus EHW-S55P3B-PNUS:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4
After wiring is installed, fill the wiring hole with putty.
CAUTION
Fill the gaps around bundled wires with putty.
5
Connect the reverse power flow CT to the reverse power flow CT cable.
Reverse Power
Flow CT Cable
6
Connect the reverse power flow CT to the L1 and L2 phases so that electricity
purchases and sales can be monitored and recorded.
● Each cable is labeled.
● The CT has L1 and L2 sides.
Check the labels on the reverse power flow CT cable before installation.
● The CT has polarity. When fitting the CT onto the electric wire, orient the CT so that the "K"
(power supply side) indication is on the side of the power meter.
L1 Harness
K: Power
Supply Side
CT
L: Load Side
● See the Reverse Power Flow CT Installation Diagram on
18
Page 21 regarding installation.
Red & White
Black & White
L1
L1
N
N
L2
L2
(Red)
(Red)
(White) (Black)
(White) (Black)
K: Power
L: Load Side
L2 Harness
Supply Side
The reverse power flow CT is a split core type.
It can be installed after the electric wire is
connected to the terminal.
Putty
Reverse Power
Flow CT
Back Side