+00EH99858901_01EN_4-way_IM_printOnly.book Page 36 Tuesday, December 4, 2007 2:31 PM
4-way Air Discharge Cassette Type
Check codes and parts to be checked
Wired
Wireless remote controller
remote
Sensor block display of
controller
receiving unit
display
Operation Timer Ready
Indication
GR
GR
OR
E01
E02
E03
E04
E08
E09
E10
E18
E31
F01
F02
F04
F06
F07
F08
F10
F12
F13
F15
F29
Judging
Main defective parts
device
Flashing
No header remote
controller
Remote
controller
Remote controller
communication error
Remote controller
Remote
transmission error
controller
Indoor unit-remote
controller regular
Indoor
communication error
Indoor unit-outdoor
unit serial
communication error
Indoor
IPDU-CDB
communication error
Duplicated indoor
Indoor
addresses
Duplicated header
Remote
remote controllers
controller
CPU-CPU
Indoor
communication error
Header indoor unit-
indoor follower unit
Indoor
regular communication
error
IPDU communication
Outdoor
error
Indoor unit heat
ALT
exchanger sensor
Indoor
(TCJ) error
Indoor unit heat
ALT
exchanger sensor (TC)
Indoor
error
Outdoor unit discharge
ALT
temp. sensor (TD)
Outdoor
error
Outdoor unit temp.
ALT
Outdoor
sensor (TE/TS) error
ALT
TL sensor error
Outdoor
Outdoor unit outside
ALT
Outdoor
air temp. sensor error
Indoor unit room temp.
ALT
Indoor
sensor (TA) error
ALT
TS (1) sensor error
Outdoor
ALT
Heat sink sensor error
Outdoor
Temp. sensor
ALT
Outdoor
connection error
Indoor unit, other P.C.
SIM
Indoor
board error
– 36 –
Parts to be checked / error description
Incorrect remote controller setting --- The header remote
controller has not been set (including two remote
controllers).
No signal can be received from the indoor unit.
Indoor/outdoor connecting wires, indoor P.C. board,
remote controller
--- No signal can be sent to the indoor unit.
Remote controller, network adapter, indoor P.C. board --
- No data is received from the remote controller or
network adapter.
Indoor/outdoor connecting wires, indoor P.C. board,
outdoor P.C. board --- Serial communication error
between indoor unit and outdoor unit
Indoor address setting error --- The same address as the
self-address was detected.
Remote controller address setting error --- Two remote
controllers are set as header in the double-remote
controller control.
(* The header indoor unit stops raising alarm and follower
indoor units continue to operate.)
Indoor P.C. board --- Communication error between main
MCU and motor microcomputer MCU
Indoor P.C. board --- Regular communication is not
possible between header and follower indoor units or
between twin header (main) and follower (sub) units.
Communication error between IPDU and CDB
Heat exchanger sensor (TCJ) , indoor P.C. board ---
Open-circuit or short-circuit of the heat exchanger sensor
(TCJ) was detected.
Heat exchanger sensor (TC), indoor P.C. board --- Open-
circuit or short-circuit of the heat exchanger sensor (TC)
was detected.
Outdoor temp. sensor (TD), outdoor P.C. board --- Open-
circuit or short-circuit of the discharge temp. sensor was
detected.
Outdoor temp. sensors (TE/TS), outdoor P.C. board ---
Open-circuit or short-circuit of the heat exchanger temp.
sensor was detected.
TL sensor may be displaced, disconnected or short-
circuited.
Outdoor temp. sensor (TO), outdoor P.C. board --- Open-
circuit or short-circuit of the outdoor air temp. sensor was
detected.
Room temp. sensor (TA), indoor P.C. board --- Open-
circuit or short-circuit of the room temp. sensor (TA) was
detected.
TS (1) sensor may be displaced, disconnected or short-
circuited.
Abnormal temperature was detected by the temp. sensor
of the IGBT heat sink.
Temp. sensor (TE/TS) may be connected incorrectly.
Indoor P.C. board --- EEPROM error
Installation Manual
Air
conditione
r status
*
*
Auto-reset
Auto-reset
Auto-reset
EN
*
Auto-reset
Auto-reset
Entire stop
Auto-reset
Auto-reset
Entire stop
Entire stop
Entire stop
Operation
continued
Auto-reset
Entire stop
Entire stop
Entire stop
Auto-reset
36-EN
Toshiba XXXXXXX(X/X)