Fault mode
When a fault has occurred, the ERROR
icon and the fault code will be displayed.

3.7. Faults Reference Code

Fault event
Bus start fail
Bus over
Bus under
Inverter soft start fail
Inverter voltage high
Inverter voltage Low

3.8. Warning indicator

Warning
Low Battery
Overload
Battery is not connected
Over Charge
Site wiring fault
EPO enable
Over temperature
Charger failure
Battery fault
Out of bypass voltage range
Bypass frequency unstable
EEPROM error
Fan Failure
Battery replacement
NOTE: "Site Wiring Fault" function can be enabled/disabled via software. Please check software
manual for the details.
Fault code
Icon
Fault event
01
x
Inverter output short
02
x
Battery voltage too high
03
x
Battery voltage too low
11
x
Over temperature
12
x
Over load
Charger failure
13
X
Icon (flashing)
18
Fault code
Alarm
Sounding every 2 seconds
Sounding every second
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
(At this time, UPS is off to remind users
something wrong with battery)
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
Sounding every 2 seconds
EN
Icon
14
27
28
x
41
43
x
45

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vfi 1500rm lcdVfi 2000rm lcdVfi 3000rm lcd

Table des Matières