Honeywell VR2 Serie Mode D'emploi page 27

Vannes papillon à siège résistant à raccords à oreilles
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3
24 VAC Transformer
Line
Blk
Volts
Red
Ω 500 Ω
1/4 watt
(–)
Control Signal
(+)
Wh t
4 to 20 mA or 2 to 10 VD C
7
Pnk
Org
VDC / 4 to 20 mA
Fig. 36. Wiring for MBS7...1,3 and MBP7...2,3,4,5,R actuators (Not all models have Switches)
24 VAC Transformer
Line
Volts
(–)
2 to 10 VDC
Feedback Signal (+)
a
Function
100%
Max
On/Off
FC
A – AB = 0%
POP
CCW
CW
On/Off
24V AC/DC
VR2, VR3, VR4, VR5 RESILIENT SEAT BUTTERFLY VALVES WITH LUGGED CONNECTIONS
18
24 VAC Transformer (AC Only)
Line
Common
(1)
Volts
(2)
+ Hot
(–)
(3) Y
Input, 2 to 10V
Control Signal
1
(+)
2-10 VDC or 4 to 20 mA
(4) Y
Input
2
7
(5) U
Output, 2 to 10
Min*
Mid*
Max*
Normal**
* Default selectable 0-100%. See Configuration Data Sheet
** Customizable. See Configuration Data Sheet .
Override Control Min, Mid, Max Postions
24 VAC Transformer
3
18
Line
Blk
Commo n
(1)
Volts
Red
Hot
(2)
Wht
Y Input
(3)
8
(–)
2 to 10 VDC
Org
(5)
U Output 2 to 10V
(+)
Feedback Signal
Direction of rotation switch
Floating Point
FO
A – AB = 100%
POP
CW
CCW
FC
A – AB = 0%
0. 5
3
4
0. 1
a
b
CCW
(Y1)
(Y2)
––
Floating Point
24V AC/DC
Fig. 37. Wiring for MBE6...4,5,R actuators
18
Blk
Common
(1)
Red
+ Ho t
(2)
A
Ω
B
C
Wh t
(3) Y
Input, 2 to 10V
1
500 Ω
Pnk
(4) Y
Input
2
1/4 watt
Org
(5)
Functions
a
b
c
0%
50%
100%
Control mode acc. to Y
2
18
10
Blk (1) – Common
Red (2) + Hot
A
Wht (3) Y
Input
1
B
12
9
Org (5) U Output 2 to 10V
CCW
CCW
CW
CW
A
B
18
A
B
18
FO
A – AB = 100%
Y1
Y1
Y2
Y2
0. 5
POP
POP
0. 9
0. 1
0. 9
CW
CCW
CW
––
27
Notes:
Meets cULus requirements without the need of an
electrical ground connection
Actuators may also be powered by 24 VDC.
3
A 500 : resistor converts the 4 to 20 mA control signal
7
to 2 to 10 VDC.
Actuators with plenum rated cable do not have numbers
18
on wires; use color codes instead.
.
Notes:
Meets cULus requirements without the need of an
electrical ground connection
Actuators may be connected in parallel. Power
2
consumption and input impedance must be observed.
Actuators may also be powered by 24 VDC.
3
Control signal may be pulsed from either the Hot
8
(Source) or Common (Sink) 24 VAC line.
Contact closures A & B also can be triacs. A & B should
both be closed for the triac source and open for triac
9
sink.
For triac sink the Common connection from the actuator
must be connected to the Hot connection of the
controller. Position feedback cannot be used with a triac
10
sink controller. The actuator internal common reference
is not compatible.
IN4004 or IN4007 diode. (IN4007 supplied)
12
Actuators with plenum rated cable do not have numbers
18
on wires; use color codes instead.
31-00190EF—02

Publicité