Valve Size
in.
2
2.5
3
4
5
6
8
10
12
14
16
18
20
24
INSTALLATION
Storage of Butterfly Valve Assemblies
• Assemblies must be stored indoors, protected from the
elements.
• Materials received on job sites that have long
installation lead times should receive extra protection
from construction damage.
• Resilient seats must be protected from abrasion,
cutting and nicking, as this will damage the liner and
may cause flange area leaks.
• Electric actuators cannot be stored in wet, damp or
caustic areas.
• Do not store construction material on top of valve
assemblies.
Installation Practices
• VR series butterfly valves are designed to be installed
between ANSI 125/150 flat-faced, raised face, slip-on
or weld neck flanges.
• Valve should be installed a minimum of 10 pipe
diameters from upstream or downstream elbows,
strainers, pumps, etc.
• For chilled water, condenser water or hot water
applications, the valve should be installed with the
stem in a vertical orientation, with the actuator
mounted above the valve.
• For applications in which there is a possibility of
sediment in the flow, the valve should be installed with
the stem in a horizontal position and the bottom of the
disc should close FROM the downstream side, rather
than from the upstream side.
31-00190EF—02
Table 8. Flow Rate
DN
2 FPS
4 FPS
50
19
39
65
30
61
80
44
88
100
78
157
125
122
245
150
176
352
200
313
627
250
490
979
300
705
1410
350
959
1919
400
1253
2507
450
1586
3173
500
1958
3917
600
2820
5640
Flow Rate in GPM
6 FPS
8 FPS
59
78
92
122
132
176
235
313
367
490
529
705
940
1253
1469
1958
2115
2820
2879
3838
3760
5013
4759
6345
5875
7834
8460
11280
15 ... 20°
• Make sure the flange faces are clean and free of rust,
scale and debris to prevent damage to the liner face.
• Do NOT use flange gaskets on VR series butterfly
valves. (Fig. 23)
• Follow the recommended flange bolting sequence. (Fig.
32)
Installation using Welded Flanges
• Mount flanges on both sides of valve body and install
bolts to properly align valve body and both flanges.
• Install the valve with the disc in the "Almost Closed"
position (Fig. 22)
• Do not use any flange gaskets (Fig. 23)
• Make sure the valve liner and flange internal diameters
are in alignment. (Fig. 24)
• Take valve body / flange pair assembly and align with
piping ends.
22
10 FPS
12 FPS
98
117
153
184
220
264
392
470
612
734
881
1058
1567
1880
2448
2738
3525
4230
4798
5758
6267
7520
7931
9518
9792
11750
14100
16921
Fig. 22.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vr3 serieVr4 serieVr5 serieVr2f6lpn2/mVr2f6lpn4/mVr2f7lpf2/m ... Afficher tout

Table des Matières