3. Technical data and intended use / 4. Switch contacts
Permissible vibration load at the mounting point
The instruments should always be installed in locations free from vibration.
If necessary, it is possible to isolate the instrument from the mounting point
by installing a flexible connection line between the measuring point and the
pressure gauge and mounting the instrument on a suitable bracket.
If this is not possible, the following limit values must not be exceeded:
Dry gauges:
(Model 73)
Liquid-filled gauges:
(Model 733)
The liquid filling must be checked on a regular basis.
The liquid level must not drop below 75 % of the gauge diameter.
4. Switch contacts
EC-type examination certificates
Standard version Model 831.XX
PTB 99 ATEX 19 X (Appendix 3) and ZELM 03 ATEX 018 X (Appendix 5)
Depending on the number of switches and on the case diameter either
Model SJ2-N... or Model SJ3.5-...-N... is used.
Safety pattern version Models 831.XX - SN or - S1N
PTB 00 ATEX 049 X (Appendix 4) and ZELM 03 ATEX 018 X (Appendix 5
Depending on the number of switches and on the case diameter either
Models SJ 2-SN..., SJ 2-S1N..., SJ 3.5-SN.. or SJ 3.5-S1N... are used.
The built-in sensor type is stated on the product label of the pressure gauge.
Wiring details
The electrical connections must only be made by qualified personnel
Connection of the switches via screw terminals in the terminal box
Conductor cross section max. 1.5 mm
The terminal assignment is stated on the connection plate of the
pressure gauge
The instruments must be connected to the equipotential bonding of the plant
WIKA Operating instructions pressure gauges Model 7 with 831 per ATEX
Frequency range < 150 Hz
Acceleration < 0.7 g (7 m/s
Frequency range < 150 Hz
Acceleration < 4 g (40 m/s
)
)
GB
7