1. Safety instructions / 2. Description

1. Safety instructions

!
GB
Caution
Only work on the gauge with the voltage disconnected
Serious injuries and/or damage can occur should the appropriate regulations
not be observed
Only appropriately qualified personnel should work on these instruments

2. Description

The pressure gauges measure the pressure by means of elastic diaphragm
measuring elements
The measuring characteristics are in accordance with the EN 837-3 and
DIN 16 085 standards
In addition the Model 73X.31 also meet the requirements, relating to safety
pattern pressure gauges, outlined in the EN 837-3 (user protection) standard
The built-in electrical switch contacts are non-contact slot-type inductive
proximity sensors, which are powered from switching amplifiers with certified
intrinsically safe circuits. When any of the adjustable set points is reached, the
associated output circuits will either open or close.
As standard Model 831 slot sensors, to EC-type examination certificate
PTB 99 ATEX 19 X (see Appendix 3) and ZELM 03 ATEX 018 X (see
Appendix 5), are used
Model 831-SN and -S1N SN sensors, to PTB 00 ATEX 2049 X (see Appen-
dix 4) and ZELM 03 ATEX 018 X (see Appendix 5), are special designs with
safety features (that are not relevant to explosion protection) for special
applications
The connected loads for the switches are in accordance with EN 60 947-5-6
("NAMUR").
4
The appropriate national safety regulations (i.e. VDE 0100 /
EN 60 079-14 / EN 837-) must be observed when installing,
commissioning and operating these instruments.