10.2 Additional parameters (sub-menu EF)
Parameter Explanation
Hi
Max. value
Lo
Min. value
CoF
Offset correction
dS1
Switching delay
of SP1
dr1
Switching delay
of rP1
dS2
Switching delay
of SP2
only type:
TS...LI2UPN8X
TS...2UPN8X
dr2
Switching delay
of rP2
only type:
TS...LI2UPN8X
TS...2UPN8X
Hans Turck GmbH & Co.KG • D–45466 Mülheim an der Ruhr • www.turck.com
Options
Function
The highest temperature
is stored in the
non-volatile memory.
The lowest temperature
is stored in the
non-volatile memory.
Signifi cant thermal
changes in the sensor
environment can lead to
a measured value offset.
This drift can be
corrected.
Adjustment range:
-10 to +10 % of the
measuring span
0 / 0.1 ... 50 s in
increments of 0.1 s
(0 = delay time is
not active)
0 / 0.1 ... 50 s in
increments of 0.1 s
(0 = delay time is
not active)
0 / 0.1...50 s in
increments of 0.1 s
(0 = switching delay is
not active)
0 / 0.1...50 s in
increments of 0.1 s
(0 = switching delay is
not active)